Cisco Nexus 7000 Series Hardware Installation and Reference Guide
OL-18634-01
Chapter 4      Installing Power Supply Units
Connecting the Power Supply Units to AC Power
Connecting 6-kW Power Supply Units
To connect a 6-kW power supply unit to one or more AC power sources, follow these steps:
Step 1
Ensure that the power supply switch located on the front of the power supply is set at STBY.
Step 2
Plug one or two AC power cables into the power supply unit, and use a Phillips screwdriver to tighten 
the power cable retainer screws on the cable retention device.
Step 3
Plug the other ends of the power cables into separate AC power sources supplied by the data center.
Note
If you are using the combined power mode or power supply redundancy, you can connect both power 
cables to the same 20 A circuit. If you are using the input source redundancy mode, you must connect 
each power cable to separate 20 A circuits.
Warning
Take care when connecting units to the supply circuit so that wiring is not overloaded. Statement 1018
Warning
This product relies on the building’s installation for short-circuit (overcurrent) protection. Ensure that 
the protective device is rated not greater than: 
 
250V, 20 A 
 
Statement 1005
Step 4
Turn the power supply switch from STBY to ON.
Step 5
Verify that the power supply is receiving AC power by making sure that the INPUT and OUTPUT power 
supply LEDs are lit and the FAULT LED is not lit or blinking. For an explanation of all the power supply 
unit LEDs and the conditions that they indicate, see 
.
Note
When you first activate the power supply, you can verify the functionality of the LEDs by checking that 
each LED turns on for a couple of seconds.
If the Fault LED is blinking red, turn the power switch to STDBY, check the AC power connections on 
the power supply unit and the AC power source, and then turn the power switch back to ON. The Input 
and Output LEDs for the connected power supply units should be green and the Fault LED should be off.
Connecting 7.5-kW Power Supply Units
To connect a 7.5-kW power supply unit to one or more AC power sources, follow these steps:
Step 1
Ensure that the power supply switch located on the front of the power supply is set at STBY.
Step 2
Plug each power cable into separate AC power sources supplied by the data center.