6-35
Cisco Nexus 7000 Series Hardware Installation and Reference Guide
OL-18634-01
Chapter 6      Managing the Device Hardware
EPLD Configuration
EPLD                                Curr Ver    New Ver
-------------------------------------------------------
Power Manager                        3.4         3.6
IO                                   3.23        3.23
Inband                               1.7         1.7
Local Bus CPLD                       2.1         2.1
CMP CPLD                             6.0         6.0
WARNING: Upgrade process could take upto 30 minutes.
 
Active Supervisor is being upgraded.
Data traffic on the switch will be affected!!
The switch will reload after the upgrade process.
Do you want to continue (y/n) ? 
Step 3
Confirm the upgrade by entering Y for yes.
Do you want to continue (y/n) ? Y
\
Module 5 EPLD upgrade is successful
The Cisco Nexus 7000 Series system will reload as soon as the upgrade occurs.
Step 4
For releases 4.0(2) or earlier, if you updated the power management EPLD image, you must reset the 
power for the module so that EPLD can take effect (this is not required for release 4.0(3) or later). You 
can reset the power in one of the following two ways: 
  •
To reset the power for the module, physically remove the module and reinstall it.
Note
A module reload or just pressing the ejector buttons on the module is not sufficient for this reset 
requirement.
  •
To reset the entire system, power cycle the system. 
To confirm the EPLD upgrade, see the 
Caution
Resetting the power disrupts any data traffic going through the affected modules. If you power cycle the 
entire system, all data traffic going through the system at the time of the power cycling is disrupted. This 
is not necessary for release 4.0(3) or later.
Note
As of release 4.0(3) or later, the system automatically loads the new power management EPLD after an 
upgrade, so it is no longer necessary to reset the power for the module or system.
Upgrading EPLDs for a Fabric Module
You can upgrade EPLDs for a fabric (Xbar) module while the system is operational if at least one other 
fabric module is operational.