Cisco Nexus 7000 Series Hardware Installation and Reference Guide
OL-18634-01
Chapter 2      Installing a Cisco Nexus 7010 Chassis
Grounding the Cisco Nexus 7010 Chassis
Prerequisites for Grounding the Chassis
Before you can ground the chassis, you must have a connection to the earth ground for the data center 
building. If you installed the Cisco Nexus 7010 chassis into a bonded rack (see the rack manufacturer’s 
instructions for more information) that now has a connection to the data center earth ground, you can 
ground the chassis by connecting its grounding ports to the rack. Otherwise, you must connect the 
chassis grounding ports directly to the data center ground.
Required Tools and Equipment
To connect the system ground, you need the following tools and materials:
  •
Grounding lug—A two-holed standard barrel lug that supports up to 6 AWG wire. This lug is 
supplied with the Cisco Nexus 7010 system accessory kit.
  •
Grounding screws—Two M4 x 8 mm (metric) pan-head screws. These screws are shipped with the 
Cisco Nexus 7010 accessory kit.
  •
Grounding wire—Not supplied with the Cisco Nexus 7010 system accessory kit. This wire should 
be sized to meet local and national installation requirements. Depending on the power supply and 
system, a 12 AWG to 6 AWG copper conductor is required for U.S. installations. We recommend 
that you use commercially available 6 AWG wire. The length of the grounding wire depends on the 
proximity of the switch to proper grounding facilities.
  •
No. 1 Phillips screwdriver.
  •
Crimping tool to crimp the grounding wire to the grounding lug.
  •
Wire-stripping tool to remove the insulation from the grounding wire.
Connecting the System Ground
After you have moved the chassis into the rack or cabinet, you are ready to connect the system to the 
data center earth ground. After you ground the chassis, you can ground your ESD wrist strap by 
connecting it to the chassis.
To connect the system ground to the data center earth ground, follow these steps:
Step 1
Use a wire-stripping tool to remove approximately 0.75 inch (19 mm) of the covering from the end of 
the grounding wire.
Step 2
Insert the stripped end of the grounding wire into the open end of the grounding lug as shown in 
.
Figure 2-5
Inserting the Grounding Wire in the Grounding Lug
1
8
5
8
4
8
1
2