Cisco ME 3400 Ethernet Access Switch Hardware Installation Guide
OL-7677-04
Appendix C      Connecting to DC Power
Wiring the DC-Input Power Source
If you want to receive an alert if an external power supply fails, do not connect feeds to one terminal 
block and from there connect feeds to the second terminal block. (See the example in 
.) This 
configuration provides redundant power, and the switch continues to operate if one of the external power 
supplies fails. However, the software does not send a message to you that an internal power supply has 
failed.
Figure C-7
Connecting Feeds from One Terminal Block to the Second Terminal Block
Cisco ME 3400-24TS
 
Switches
This warning only applies to Cisco ME 3400-24TS switches:
Warning
This product relies on the building’s installation for short-circuit (overcurrent) protection. Ensure that 
the protective device is rated not greater than: 
5 A 
Statement 1005
Cisco ME 3400G-12CS Switches
This warning only applies to Cisco ME 3400G-12CS switches:
Warning
This product relies on the building’s installation for short-circuit (overcurrent) protection. Ensure that 
the protective device is rated not greater than: 
6 A 
Statement 1005
All Cisco ME 3400 Switches
These warnings apply to all Cisco ME switches:
Warning
A readily accessible two-poled disconnect device must be incorporated in the fixed wiring. 
Statement 1022
CONSOLE
SYSTEM
INPUT -36 – -72 
V
CURRENT 2 – 1A
A
B
+
+
INPUT -36 – -72 
V
CURRENT 2 – 1A
A
B
+
+
PS 1
PS 2