Chapter 3      Installation
Connecting the Switch to the Power Converter
3-30
Catalyst 2955 Hardware Installation Guide
78-14944-03
These sections describe the steps required to connect the switch to a power 
converter:
After you connect the switch to the power converter, you must connect the power 
converter to an AC or a DC power source.
For instructions on connecting the power converter to an AC power source, see 
. For 
instructions on connecting the power converter to a DC power source, see 
Installing the Power Converter on a DIN Rail
Follow these steps to install the power converter on a DIN rail.
Warning
This equipment is supplied as “open type” equipment. It must be mounted 
within an enclosure that is suitably designed for those specific environmental 
conditions that will be present and appropriately designed to prevent personal 
injury resulting from accessibility to live parts. The interior of the enclosure 
must be accessible only by the use of a tool. 
The enclosure must meet IP 54 or NEMA type 4 minimum enclosure rating 
standards. 
Statement 1063
Caution
To prevent the Catalyst 2955 switch from overheating, there must be a minimum 
of 3 inches between any other device and the top, bottom, or sides of the switch.
The power converter requires 1 inch of thermal spacing to prevent overheating. 
Therefore, there must be a minimum of 4 inches between the power converter and 
the Catalyst 2955 switch to prevent each device from overheating.