Cisco SFS 7012 InfiniBand Server Switch Hardware Users Guide 
OL-8787-04
Appendix 
Troubleshooting Scenarios
InfiniBand
This section documents common problems seen with the SFS 7012 switch.
Invalid IP Address entered for SWC via Console Port
Symptoms
Cannot access the Chassis Viewer browser window. The browser window times out and Chassis 
Viewer will not come up.
Resolution / Workaround
Invalid IP Address entered for switch card via the console port. Make sure configuration is using a 
valid IP address for the Switch (make sure initial configuration for switch is correct using the 
console port during the boot sequence).
Bad IB Cable
Symptoms
When viewing the IB fabric with a subnet manager viewer, no nodes will be seen, or only the nodes 
that have a good IB connection will be seen.
Resolution / Workaround
Possibly a bad IB cable(s). Ensure that there is a Blue LED illuminated on the leaf module IB ports 
of the SFS 7012 switch. Make sure that all devices (nodes) can be seen in the subnet manager 
window. 
Improperly Seated IB Cable
Symptoms
When viewing the Subnet Manager no nodes will be seen, or only the nodes that have a good IB 
connection will be seen.
Resolution / Workaround
Possibly an improperly seated IB cable(s). Ensure that there is a Blue LED illuminated on the 
switch. Make sure that all devices (nodes) can be seen in your Subnet Manager window.