3-36 Cisco IGX 8400 Series Installation and Configuration
Making Frame Relay Connections
Step 2
From a control terminal or a Cisco WAN Manager NMS workstation, to the node and
enter the addalmslot command followed by the slot number where the ARM is located.
This will activate the alarm reporting from the card.
Step 3
Observe that the ACTIVE LED on the ARM card is on.
Step 4
Testing the operation of the alarm outputs requires you to create an alarm and note the
resulting alarm output. This test is easy on a node that is not connected to the network but
difficult on a node in a fully operational network. The best time to create a major alarm
an operational network is during a low traffic period. If you create an alarm, go to Step 5.
Otherwise, stop here.
Step 5
Create an alarm by disconnecting a trunk cable from the connector on a back card.
Step 6
Observe that a lit MAJOR LED appears on the front of the ARM.
Step 7
Using a voltage/ohm meter (VOM), make sure continuity exists between pins 16 and 17
and between pins 35 and 36 at the DB-37 connector on the ARI card.
Step 8
Reconnect the cable that was disconnected in Step 5.
Step 9
With the VOM, check that the reading between pins 16 and 17 and pins 35 and 36 are
open and the MAJOR LED is not on.
Alarm output connections are made at the DB37 connector on the ARI card. The connector pin
assignments with the alarm signal names are listed in Table 3-1. (See Appendix C, “Cabling
Summary.
”)
Table 3-1
ARI Alarm Connector PinOuts
Pin No.
Alarm Type
Alarm Name
Alarm Description
1
both
CHASSIS
Protective ground
3
Network
NWMAJA
Major—normally open contact
22
Network
Major—normally closed contact
4
Network
NWMAJC
Major—common contact
10
Node
MNVISA
Minor Visual—normally open contact
11
Node
Minor Visual—normally closed contact
12
Node
MNVISC
Minor Visual—common contact
16
Node
MJAUDC
Major Audible—common contact
17
Node
MJAUDA
Major Audible—normally open contact
23
Network
NWMINA
Minor—normally open contact
24
Network
Minor—normally closed contact
25
Network
NWMINC
Minor—common contact
29
Node
NWAUDA
Minor Audible—normally open contact
30
Node
Minor Audible—normally closed contact
31
Node
NWAUDC
Minor Audible—common contact
35
Node
MJVISC
Major Visual—common contact
36
Node
MJVISA