Web Manager for Administrators
167
                                 Access
 
 
5. In the “Add/Edit User x Outlets” dialog box, do the following as 
appropriate.
a. Enter the username in the “User” field.
b. Enter or modify the numbers of the outlets to which the user is assigned 
in the “Outlets” field.
Use a comma to separate outlet numbers, and use a hyphen to indicate a 
range of outlets (for example: 1, 3, 6, 9-12). 
6. Click OK. 
7. Click “apply changes.” 
Configuration
On the “Configuration” form under Access>IPDUPower Management in 
Expert mode, you can specify the following:
Whether syslog messages are generated for power management events
Over current protection:
• An alarm threshold
• Whether a buzzer sounds whenever the current exceeds the defined 
threshold. 
You can define the alarm threshold for both a master and a slave unit and 
define aliases for each connected IPDU.
The Configuration form shows the ports that are currently connected to 
IPDUs. The following figure displays an example form that appears for a 
KVM/net with an AlterPath PM connected to AUX port.