 iRIS 220 / iRIS 320, V1.19 User Guide - 34 
 
34
 
iQuest (NZ) Ltd  - PO Box 15169, Hamilton, New Zealand  Tel: +64 7 857-0810  Fax: +64 7 857-0811  Email: iquest@iquest.co.nz
 
 
Option 4 
When  this  option  is  selected  you  will  be  prompted  to  enter  a  scaling  multiplier.    This  multiplier  is  used  to 
convert the raw input into engineering units. 
 
> Multiplier= 
 
 
Option 5 
When this option is selected you will be prompted to enter a scaling offset.  This offset is added to the scaled 
engineering value. 
 
> Offset= 
 
 
Option 6 
When  this option  is selected  you  will  be  prompted  to  enter a  logging multiplier  to convert  from engineering 
units to an integer value to storage in the logging memory. 
 
> Log Multiplier= 
 
For example, if you need to log a measurement that is accurate to two decimal places you will need to enter 
a logging multiplier of 100. 
 
NOTE: Care needs to be taken in the selection of an appropriate logging multiplier because the iRIS 
logs  data  as  signed  16-bit  integer  values  (-32768  to  32767).  This  means  that  the  maximum  scaled 
value multiplied by the logging multiplier must not exceed 32767. 
 
 
Option 7 
When this option is selected you will be prompted to enter a logging rate (in minutes) for the sensor. 
 
> Log Rate= 
 
If you wish to log digital data on change of state you can enter a value of 0.  If this parameter is left at 0 for 
Analog sources, they will not be logged. 
 
 
Option 8 
Select this option to display the Alarm Configuration menu for the sensor. 
 
 
Option 9 
Select this information to view the logged data for the sensor. You will be prompted to enter the number of 
samples you would like returned 
 
NOTE: This option is only available when the terminal session is through the RS232 port, not through 
a GPRS/CDMA-1X terminal session.