6.2 Connecting a 0-5V Pressure Transducer 
 
Connecting  a  standard  sensor  (such  as  a  pressure  transducer  that  provides  a  0-5V  signal)  to  an  iRIS  is 
relatively  straightforward.    The  sensor  can  be  powered  from  the  iRIS  320’s  12V  supply  and  optionally 
controlled by a digital output to save power.  
 
However, the iRIS 320’s internal battery is NOT recommended for directly powering the sensor alone if the 
charging  source  is  a  solar  panel,  as  it  is  a  relatively  low  capacity  type.  Connect  a  supplementary  external 
12V battery (7A/Hr or larger) to increase the available storage. 
 
The diagram below shows the typical connection diagram for such an installation.  It assumes the use of AI1 
as  the  desired  input  channel.  It  also  shows  the  connection  of  a  transistor  switch  module  with  control  from 
DO1. 
 
TOP 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
BOTTOM 
 
iRIS  I/O Connector 
 
 
 
The sensor should be configured for the correct channel, scaling and logging regime as described in section 
4.3.8. 
 
NOTE:  The iRIS supports activation of one or both digital outputs with a schedule. See section 4.3.12 
for  more  details  and  an  example.    Therefore,  if  further  power  reduction  is  to  be  achieved  by 
controlling the transducer power, follow this procedure: 
 
1. 
Install a transistor switch module in series with the transducer power lead and control it from 
one of the digital outputs. See Appendix A for details on the transistor switch module. 
 
2. 
Configure the digital output’s mode to be Schedule (Mode = 1). 
 
3. 
Set up the digital output’s schedule to match the sensor’s logging period, but with the digital 
output being set to activate the desired amount of time before the sensor is to log and with 
sufficient “on” time to ensure an overlap with the logging time. 
 
4. 
Ensure the sensor mode is set to 0 (Instant). 
 

Signal      Pressure Transducer 
Optional 
Transistor 
Switching 
Module
 
Charging source e.g solar panel 
  -               + 
External 
12V Battery 
(Required)