7 Analogue Input Scaling 
This  section  explains  the  recommended  procedure  to  use  when  scaling  an  analogue  input  (voltage  or 
current). It makes use of the scaling calculator provided in the iLink utility.  However, the calculation can be 
done manually using this formula. NOTE: mV = Input mV, EU = Engineering Units (scaled output e.g metres) 
 
Multiplier = (Maximum EU – Minimum EU) / (Maximum mV – Minimum mV) 
Offset       = Maximum EU - (Multiplier * Maximum mV) 
 
7.1 Example: A 4-20mA Water Level Sensor 
In this example, we have a water level instrument connected to the iRIS Analogue Input 1. This instrument is 
designed to provide a nominal 4-20mA signal for a 0-10 metre water level range. However, in the real world, 
most instruments are not exact and a small difference in actual signal may occur. In addition, the current sink 
resistor should ideally be 250
Ω
 (giving 5V at 20mA), but only a 249
Ω
 part was available. There is also the 
small  reduction  in  resistance caused  by  the  internal  input  impedance  of  the  iRIS  input channel  to  take  into 
account (see Section 3.4.4 Analogue Inputs). Therefore the voltage measured by the iRIS for a given water 
level is slightly different. 
 
1. 
Power up the installation and allow to stabilize.  
2. 
Set the instrument to zero water level (using a calibrator) 
3. 
Note  the  actual  voltage  measured  by  the  iRIS  (view  this  on  the  LCD  on  “System  Status  3” 
screen. See Section 5.2.5. The LCD screen example below shows 993mV for a 0m input level. 
4. 
Now  increase  the  instrument  input  to  full  scale  (10m)  using  the  calibrator.  Again,  note  the 
measured voltage relating to this input level. This time it is 4961mV for a 10m level input. 
 
 
 
 
 
 
5. 
Using the iLink Scaling Calculator, enter the minimum and maximum measured voltages and the 
levels  they  represent  in  the  appropriate  fields.  Click  the  “Calculate”  button  to  generate  the 
correct multiplier and offset parameters to use in the sensor setup menu for Sensor 1 as shown. 
 
 
 
AI1:  993 mV 
AI2:    0 mV 
AI3:    0 mV 
AI4:    0 mV 
 
AI1: 4961 mV 
AI2:    0 mV 
AI3:    0 mV 
AI4:    0 mV 
 
*  Sensor 1 Cfg 
(Now:  0.000) 
0  Exit 
 
 
 
1  Source [1: Analog 1] 
2  Name [Water Lvl] 
3  Mode [Period Avg] 
4  Multiplier [ 0.00252]  
5  Offset [   -2.50252]   
6  Log Multiplier [1000]  
7  Log Rate [15min] 
 
8  Alarms 
 
 
 
9  Data 
 
 
 
 
>
 
 
Min mV 
Max mV 
Max WL 
Min WL