1-1     Installation 
Connectivity Module 
 
 
How to Install the Connectivity Module 
on 7000 & 4000 Series and Series 300 ATSs 
 
The Connectivity Module (CM) mounts on a DIN rail 
under the ATS Controller (Group 5 & 1). A short serial 
cable connects the CM to the Controller. If a Power 
Manager (PM) or Digital Power Meter (DPM) is present, 
a long serial cable connects the CM to the PM.  Refer to 
installation drawings provided and follow the steps below 
to install the Connectivity Module. 
 
Connectivity Module Kit 
K889950 
for 7000 & 4000 Series 
and Series 300 only 
Connectivity Module Kit 
K889950-001 for 
7000 & 4000 Series 
and Series 300 
with PM or DPM 
Connectivity 
Module 5150 
629800-004 
Connectivity 
Module 5150 
629800-004 
DIN Rail and 
Hardware 
754607 
DIN Rail and 
Hardware 
754607 
10-in. Serial 
Cable for 
Controller 
629798-001 
10-in. Serial 
Cable for 
Controller 
629798-001 
  4-ft 
Serial 
Cable for  
PM or DPM * 
629798-002 
 
* A 9-foot serial cable (629798-004) is 
required for G7ATB, G7ACTB, G7ADTB. 
 
 
 
To avoid possible shock, burns, or death, deenergize all 
electrical sources to the ATS before installing the 
Connectivity Module. 
 
1.  De-energize both Normal and Emergency sources 
that feed the ATS. Open enclosure door and check 
with a non-contact AC voltage detector. 
 
2.  Mount the DIN rail (supplied in the kit) onto two 
studs (on the door) below the Controller. 
 
Connectivity Module will mount on the right side.  
 
3.  Install Connectivity Module onto DIN rail by 
hooking the bottom of module on bottom of DIN rail 
and rocking it upward unit it snaps in place.  
 
4.  Install the 10-inch serial cable between the Controller 
receptacle (J7 on Group 5, J4 on Group 1) and the 
Connectivity Module J1 receptacle.  
 
5.  If a PM (or DPM) is present, connect the 4-foot serial 
cable between the PM J5 receptacle (or DPM J2 
receptacle) and the Connectivity Module J2 
receptacle.*  
 
Now test communications (go to page 1-2). 
 
How to Install the Connectivity Module 
on ASCO 940/962 ATSs 
 
The Connectivity Module (CM) mounts on a DIN rail 
near the ATS Control Panel. A separate power supply is 
needed unless it is connected to a Power Manager (PM). 
Group 6A/7A Control Panel must have a Serial 
Communication Kit added. A single communication 
cable (2 twisted pairs and overall shield connects the CM 
to the Control Panel). Refer to installation drawings 
provided and follow the steps below to install the 
Connectivity Module. 
 
Connectivity Module Kit 
K889953 
for ASCO 940/962 only
 
Connectivity Module Kit 
K889953-001 
for ASCO 940/962 with PM
 
Connectivity 
Module 5150 
629800-004 
Connectivity 
Module 5150 
629800-004 
DIN Rail and 
Hardware 
754610 
DIN Rail and 
Hardware 
754610 
Serial Com. 
Kit for Group 
6A/7A CP * 
467508 
Serial Com. 
Kit for Group 
6A/7A CP * 
467508 
  Serial 
Cable 
for PM 
629798-002 
* Serial communication & transient protection boards. 
 
Required 
Power Supply ** 
not supplied
 
Communication Cable 
(4 wires and an overall shield) 
not supplied
 
24 Vdc, 80 mA ** use 
16 AWG wire 
Belden 9842, 9829, 89729, 82729 or 
Alpha 6202C, 6222C, 58902 only 
 
** If a Power Manager (PM) is present, a power supply is not needed for 
the Connectivity Module (CM). The serial cable from the PM provides 
the power to the CM. 
 
 
 
 
To avoid possible shock, burns, or death, deenergize all 
electrical sources to the ATS before installing the 
Connectivity Module. 
 
1.  De-energize both Normal and Emergency sources 
that feed the ATS. Open enclosure door and check 
with a non-contact AC voltage detector. 
 
2.  Mount DIN rail (supplied in the kit) onto two studs 
(on the door) below or adjacent to the Control Panel.  
 
3.  Install the Connectivity Module onto DIN rail. 
 
4.  Prepare and connect the specified communication 
cable between the Control Panel terminals and the 
Connectivity Module J4 terminals as listed below: 
 
5.  Prepare and connect the 24 Vdc power supply to the 
Connectivity Module. Use 16 AWG wiring to J5 
terminal plug (1 is + positive, 2 is – negative).  
 
Now test communications (go to page 1-2). 
    
DANGER 
 
 
 
 
   
DANGER
!