3-1     Series 300 ATSs 
Connectivity Module 
 
 
Device Configurator Screen for Series 300 ATSs 
 
The  Device Configurator Screen for Series 300 ATSs shows the Group 1 controller 
configuration settings (right side) and the Connectivity Module (server) configuration 
settings (left side) for the selected ATS.  
 
Group 1 Controller Configuration (right side) 
Enter or change the ATS Name (8 char. max.) and the ATS Location (20 char. max.). Press 
the Update button when finished to save the Group 1 controller configuration changes. 
 
Connectivity Module (server) Configuration (left side) 
Several configuration settings must be set appropriately as described below. Press the Update 
Server
 button when finished to save configuration changes. 
 
 
Device Configurator Screen for Series 300 ATSs 
 
 
When a Power Manager or Digital Power Meter is connected, additional buttons appear at the bottom of the 
Connectivity Module Device Configuration screen. 
Additional Buttons on Device Configurator Screen for 
Series 300 ATSs with Power Manager or Digital Power Meter  
 
 
ATS Location 
ATS Name 
Serial Port Speed   9600 
Consult with your network 
administrator for these 4 settings: 
  IP Address 
  Subnet Mask 
  Gateway Address 
  TCP Port Number 
   (Range of ports allowed is: 
   1024-65535, but do not use 
   ports 14000-14009 or 30718) 
Press Update button when finished to 
save the configuration changes. Do this 
before you press Update Server button. 
After Controller or has been updated, 
press Update Server button to save 
the configuration changes. 
Flow Control   No flow control 
Interface Mode  RS485-4 or 2 Wire 
Encyrption   enable check box 
and assign an AES port (same 
range as TCP port but do not use 
the same port number used for 
TCP port.)
 
Press to configure the Power 
Manager or Digital Power Meter. 
Press to configure the Group 1 Controller. 
After Controller, PM, or DPM has been 
updated, press Update Server button 
to save the configuration changes.
SNMP  refer to Appendix A-5