Connectivity Module 
ASCO 940/962 ATSs     4-1 
 
 
Device Configurator Screen for ASCO 940/962 ATSs 
 
The  Device Configurator Screen for ASCO 940/962 ATSs shows the Group 7A controller configuration 
settings (right side) and the Connectivity Module (server) configuration settings (left) for the selected ATS.  
 
Group 7A Controller Configuration (right side) 
Enter or change the ATS Name (18 char. max.) and ATS Nominal Voltage (must be entered to get correct 
reading). Press the Update button when finished to save the Group 7A controller configuration changes. 
 
Connectivity Module (server) Configuration (left side) 
Several configuration settings must be set appropriately as described below. Press the Update Server button 
when finished to save configuration changes. 
 
 
Device Configurator Screen without Power Manager 
 
 
 
Device Configurator Screen with Power Manager  
 
 
Nom. Voltage
ATS Name 
Serial Port Speed   9600 
Consult with your network 
administrator for these 4 settings: 
  IP Address 
  Subnet Mask 
  Gateway Address 
  TCP Port Number 
   (Range of ports allowed is: 
   10024-65535, but do not use 
   ports 1400-14009 or 30718) 
Press Update button 
when finished to save 
the configuration 
Press Update Server button 
when finished to save the 
configuration changes. 
Flow Control   No flow control 
Interface Mode RS485-4 or 2 Wire 
Nom. Voltage
ATS Name 
Serial Port Speed   9600 
Consult with your network 
administrator for these 4 settings: 
  IP Address 
  Subnet Mask 
  Gateway Address 
  TCP Port Number 
   (Range of ports allowed is: 
   10024-65535, but do not use 
   ports 1400-14009 or 30718) 
Press Update button 
when finished to save 
the configuration 
Press Update Server button 
when finished to save the 
configuration changes. 
Flow Control   No flow control 
Interface Mode  RS422/485-4Wire 
Encyrption   enable check box and 
assign an AES port (same range as 
TCP port but do not use the same 
port number used for TCP port.)
 
Encyrption   enable check box and 
assign an AES port (same range as 
TCP port but do not use the same 
port number used for TCP port.)
 