10  Engineering Information 
Issue 03/01 
 
MICROMASTER 411 & COMBIMASTER 411    Operating Instructions  
132 
6SE6400-5CA00-0BP0  
If the active current falls below the normalized threshold P2395, then the setpoint is 
linearly decreased as a function of the active current. 
 
P2396
P2395
 
1
m
=
 
This reduction causes the motor to be powered-down and in turn the system (e.g. 
pump), as long as the actual value (e.g. actual pressure) does not fall below the 
threshold px. 
If the actual value falls below threshold px, while the setpoint is decreased via the 
active current, the decrease is stopped and the original setpoint p* is again re-
established. 
If the actual value falls below threshold px after the motor was shutdown, the 
inverter automatically powers-up again without having to toggle the ON command. 
10.3 Braking 
Reducing the output frequency of the inverter will cause the motor to slow down 
and as the frequency is gradually reduced to zero the motor will stop. Reducing the 
output frequency too rapidly may cause the motor to act as a generator and cause 
a negative current (regeneration) to return to the DC link. To overcome this 
possibility the MICROMASTER 411/COMBIMASTER 411 employs a number of 
methods to control braking. These options are described in the following 
paragraphs. 
The method of bringing the motor to a standstill is selected by the user depending 
on operational requirements. 
Normal Braking 
The usual or normal braking method is to allow the motor to come to a standstill at 
the selected ramp-down rate (OFF1), to coast to a standstill (OFF2) or to quickly 
ramp down (OFF3) without applying any additional braking. (Refer to parameters 
P0701, P0702 and P0703). However, if regeneration does cause tripping, DC or 
Compound braking methods may be considered. 
 
Figure 10-13  Frequency Ramp Down