Siemens 6ED1050-1AA00-0BE8 Manual De Usuario
Programming LOGO!
3.7 Writing and starting the circuit program
LOGO!
Manual, 04/2011, A5E03556174-01
Manual, 04/2011, A5E03556174-01
109
3.7.12
Defining the type of analog outputs
Analog outputs can be either 0..10V/0..20mA, which is the default, or 4..20mA.
To define the type of analog outputs, follow these steps starting from the programming
To define the type of analog outputs, follow these steps starting from the programming
menu:
0VJ&RQILJ
3DVVZRUG
&OHDU3UJ
!(GLW
1. Move the ">" cursor to "
①
": Press or
2. Select "
①
": Press OK
3. Move the ">" cursor to 'AQ': Press or
4. Select 'AQ ': Press OK
5. Move the ">" cursor to "
4. Select 'AQ ': Press OK
5. Move the ">" cursor to "
②
": Press or
!$47\SH
$4LQ6WRS
6. Select "
②
": Press OK
LOGO! shows the following display, for example:
$4P$
$4GHIDXOW
The defined type for each analog channel is shown. To change the type, continue as
follows
7. Move to the AQ that you want to change. Press or
8. Select either default (0..10V/0..20mA) or 4..20mA. Press or
9. Confirm your selection. Press OK
8. Select either default (0..10V/0..20mA) or 4..20mA. Press or
9. Confirm your selection. Press OK