Siemens 6ED1050-1AA00-0BE8 Manual De Usuario

Descargar
Página de 372
Programming LOGO! 
 
3.7 Writing and starting the circuit program 
 
LOGO! 
116
 
Manual, 04/2011, A5E03556174-01 
3.7.15 
Synchronization 
Time synchronization between LOGO! and a connected communication module EIB/KNX 
(version 0AA1 upwards!) can be enabled/disabled  
●  in parameter assignment mode by means of the set menu ("Clock" menu item) 
●  in programming mode by means of the setup menu ("Clock" menu item). 
When synchronization is enabled, LOGO! can receive the time-of-day from a communication 
module EIB/KNX (version 0AA1 upwards). 
Whether synchronization is enabled or disabled, the time-of-day is always sent to the 
expansion modules at power-up, every hour (STOP mode or RUN mode), and when the time 
of day is changed (after a 'Set Clock' is executed or after a summertime/wintertime 
conversion). 
 
 
Note 
When using a LOGO! Base Module with digital or analog expansion modules, but without 
communication module EIB/KNX (version 0AA1 upwards), time synchronization must not be 
activated! You must check whether time synchronization is deactivated ('Sync' must be set to 
'Off'). 
 
To enable/disable synchronization in programming mode: 
1.  Switch LOGO! to programming mode. LOGO! displays the main menu. 
6WDUW
6HWXS
&DUG
!3URJUDP
 
2.  Select "
": Press   or   
3.  Confirm "
": Press OK 
%0$,180
0HQX/DQJ
/&'
!&ORFN
 
4.  Move the '>' cursor to "
": Press   or   
5.  Confirm "
": Press OK 
6\QF
6:7LPH
!6HW&ORFN
 
6.  Move the '>' cursor to "
": Press   or   
7.  Apply "
": Press OK