Programming LOGO! 
 
3.9 Memory space and circuit program size 
 
LOGO! 
130
 
Manual, 04/2011, A5E03556174-01 
3.9 
Memory space and circuit program size 
The size of a circuit program in LOGO! is limited by the memory space (memory used by the 
blocks).    
Memory areas 
●  Program memory: 
LOGO! allows only a limited number of blocks in your circuit program. 
The second limitation is based on the maximum number of bytes a circuit program may 
contain. The total number of bytes used can be determined by adding up the number of 
bytes used for the relevant function blocks.  
●  Retentive memory (Rem): 
In this area, LOGO! stores values which need to be retentive; for example, the hours 
counter value. Blocks with optional retentivity use this memory area only if this function is 
actually enabled. 
 
 
Note 
LOGO! supports a maximum of one million write cycles. LOGO! counts every power-off, 
program downloading from LOGO!Soft Comfort to LOGO!, program creation from LOGO!, 
or menu setting as one cycle.  
Resources available in LOGO! 
A circuit program in LOGO! can occupy the following maximum resources: 
 
LOGO! device series 
Bytes 
Blocks 
REM 
LOGO! 0BA6 
3800 
200 
250 
LOGO! 0BA7 
8400 
400 
250 
LOGO! monitors memory utilization, and offers only those functions from the lists for which it 
can actually provide sufficient memory space.