LOGO! functions 
 
4.4 Special functions list - SF 
LOGO! 
Manual, 04/2011, A5E03556174-01 
201
 
4.4.15 
Up/down counter 
Short description 
An input pulse increments or decrements an internal value, depending on the parameter 
setting. The output is set or reset when a configured threshold is reached. The direction of 
count can be changed with a signal at input Dir.     
 
Symbol in LOGO! 
Wiring 
Description 
Input R 
A signal at input R resets the internal count value to 
zero. 
Input Cnt 
The function counts the 0 to 1 transitions at input Cnt. 
1 to 0 transitions are not counted. 
Use  
• 
inputs I3, I4, I5, and I6 for fast counting (only 
LOGO! 12/24RC/RCo, LOGO! 12/24RCE, LOGO! 
24/24o and LOGO! 24C/24Co): max. 5 kHz, if the 
fast input is directly connected to the up/down 
counter function block 
• 
any other input or circuit component for counting 
low frequency signals (typ. 4 Hz). 
Input Dir 
You set the direction of count at input Dir: 
Dir = 0: Count up 
Dir = 1: Count down 
Parameter 
On: On threshold 
 Range of values: 
 0...999999 
Off: Off threshold 
 Range of values: 
 0...999999 
StartVal: Initial value from which to begin counting 
either down or up. 
Retentivity for internal counter value Cnt:  
/ = No retentivity 
R = The status is retentive. 
4
5
&QW
'LU
3DU
 
Output Q 
Q is set or reset, depending on the current value at 
Cnt and the set thresholds.