Siemens 6ED1050-1AA00-0BE8 Manual De Usuario

Descargar
Página de 372
 
LOGO! functions 
 
4.4 Special functions list - SF 
LOGO! 
Manual, 04/2011, A5E03556174-01 
213
 
4.4.18 
Analog threshold trigger 
Short description 
The output is set and reset at two configurable thresholds.      
 
Symbol in LOGO! 
Wiring 
Description 
Input Ax 
Input Ax is one of the following analog signals:  
• 
AI1 to AI8 (*) 
• 
AM1 to AM6 (if 0BA6) or AM1 to AM16 (if 0BA7) 
• 
NAI1 to NAI32 (if 0BA7) 
• 
AQ1 to AQ2 
• 
NAQ1 to NAQ16 (if 0BA7) 
• 
Block number of a function with analog output 
Parameter 
A: Gain 
 Range of values: ±10.00 
B: Zero offset 
 Range of values: ±10,000 
On: On threshold 
 Range of values: ±20,000 
Off: Off threshold 
 Range of values: ±20,000 
p: Number of decimals 
 Range of values: 0, 1, 2, 3 
$
4
$[
3DU
 
Output Q 
Q is set or reset by the threshold triggers. 
* AI1...AI8: 0...10 V corresponds with 0...1000 (internal value). 
Gain and offset parameters 
Please note the information on gain and offset parameters in topic "Calculating the gain and 
Parameters On and Off 
The On and Off parameters can be provided by the actual value of another already-
programmed function. You can use the actual values of the following functions:  
●  Analog comparator (Page 218) (actual value Ax – Ay) 
●  Analog amplifier (Page 226) (actual value Ax) 
●  Analog multiplexer (Pag248) (actual value AQ) 
●  Analog Ramp (Page 251) (actual value AQ) 
●  Mathematic instruction (Page 265) (actual value AQ) 
●  PI controller (Page 256) (actual value AQ) 
●  Up/down counter (Pag201) (actual value Cnt)