Siemens 6ED1050-1AA00-0BE8 Manual De Usuario
LOGO! functions
4.4 Special functions list - SF
LOGO!
216
Manual, 04/2011, A5E03556174-01
4.4.19
Analog differential trigger
Short description
The output is set and reset depending on a configurable threshold and a differential value.
Symbol in LOGO!
Wiring
Description
Input Ax
Input Ax is one of the following analog signals:
•
•
AI1 to AI8 (*)
•
AM1 to AM6 (if 0BA6) or AM1 to AM16 (if 0BA7)
•
NAI1 to NAI32 (if 0BA7)
•
AQ1 to AQ2
•
NAQ1 to NAQ16 (if 0BA7)
•
Block number of a function with analog output
Parameter
A: Gain
Range of values: ±10.00
B: Zero offset
B: Zero offset
Range of values: ±10,000
On: On/Off threshold
On: On/Off threshold
Range of values: ±20,000
Δ: Differential value for calculating the off parameter
Δ: Differential value for calculating the off parameter
Range of values: ±20,000
p: Number of decimals
p: Number of decimals
Range of values: 0, 1, 2, 3
$
˂
4
$[
3DU
3DU
Output Q
Q is set or reset, depending on the threshold and
difference values.
* AI1...AI8: 0...10 V corresponds with 0...1000 (internal value).
Gain and offset parameters
Please note the information on gain and offset parameters in topic "Calculating the gain and
Parameter p (number of decimals)
Applies only to the display of On, Off and Ax values in a message text.
Timing diagram A: Function with negative difference Δ
$[
4
2II 2Q˂
2Q