Siemens 6ED1050-1AA00-0BE8 Manual De Usuario

Descargar
Página de 372
LOGO! functions 
 
4.4 Special functions list - SF 
 
LOGO! 
226
 
Manual, 04/2011, A5E03556174-01 
View in parameter assignment mode (example): 
$[
$HQ
%
4 $[LVRXWRIWKHUDQJHRI
$HQෙWR$HQෙ
 
%
 
4.4.22 
Analog amplifier 
Short description 
This special function amplifies the value of an analog input and outputs the result at an 
analog output.     
 
Symbol in LOGO! 
Wiring 
Description 
Input Ax 
Input Ax is one of the following analog signals:  
• 
AI1 to AI8 (*) 
• 
AM1 to AM6 (if 0BA6) or AM1 to AM16 (if 0BA7) 
• 
NAI1 to NAI32 (if 0BA7) 
• 
AQ1 to AQ2 
• 
NAQ1 to NAQ16 (if 0BA7) 
• 
Block number of a function with analog output 
Parameter 
A: Gain 
 Range of values: ±10.00 
B: Zero offset  
 Range of values: ±10,000 
p: Number of decimals 
 Range of values: 0, 1, 2, 3 
$ᇄ
$4
$[
3DU
 
Output AQ 
This special function has an analog output! This 
output can only be connected with the analog input of 
a function, an analog flag or an analog output 
connector (AQ1, AQ2). 
Range of values for AQ: 
-32767...+32767 
* AI1...AI8: 0...10 V corresponds with 0...1000 (internal value).