LOGO! functions 
 
4.4 Special functions list - SF 
LOGO! 
Manual, 04/2011, A5E03556174-01 
229
 
4.4.24 
Pulse relay 
Short description 
A short pulse at the input sets and resets the output.    
 
Symbol in LOGO! 
Wiring 
Description 
Input Trg 
You set and reset output Q with a signal at input Trg 
(Trigger). 
Input S 
You set output Q with a signal at input S. 
Input R 
You reset output Q with a signal at input R. 
Parameter 
Selection: 
 RS (R input priority) or 
 SR (S input priority) 
Retentivity: 
/ = No retentivity 
R = The status is retentive. 
56
4
7UJ
6
5
3DU
 
Output Q 
Q is set with a signal at Trg, and reset with the next 
signal at Trg, if S and R = 0. 
Timing diagram  
6
5
4
7UJ
7KHEROGSULQWHGVHFWLRQRIWKH
WLPLQJGLDJUDPLVDOVRVKRZQ
LQWKHV\PEROIRUWKHSXOVH
UHOD\
 
Functional description 
Output Q changes its status; that is, the output is set or reset with each 0 to 1 transition at 
input Trg and if the inputs S and R = 0.  
The signal at input Trg does not influence the special function when S or R = 1. 
You set the pulse relay with a signal at input S. The output is set hi. 
You reset the pulse relay with a signal at input R. The output is set lo.