LOGO! functions 
 
4.4 Special functions list - SF 
LOGO! 
Manual, 04/2011, A5E03556174-01 
243
 
4.4.26 
Softkey 
Short description 
This special function has the effect of a mechanical pushbutton or switch.   
 
Symbol in LOGO! 
Wiring 
Description 
Input En 
Output Q is set with a 0 to 1 transition of the signal at 
input En (Enable), and if 'Switch=On' was confirmed 
in parameter assignment mode. 
Parameter 
Programming mode: 
Selecting the function for pushbutton action for the 
duration of one cycle, or for switching action. 
Start: On or off state, initialized at the first start of the 
program if retentivity is disabled. 
Retentivity:  
/ = No retentivity 
R = The status is retentive. 
Parameter assignment mode (RUN mode): 
Switch: Switches the momentary pushbutton (switch) 
on or off. 
4
(Q
3DU
 
Output Q 
Switches on if En=1 and Switch=On was confirmed 
with OK. 
Factory setting 
The default parameter setting is switching action. 
Timing diagram 
4
(Q
6ZLWFK
 
Functional description 
In parameter assignment mode, the output is set with a signal at input En, if the 'Switch' 
parameter is set to 'On' and confirmed with OK. Whether the function was configured for 
pushbutton or switching action is of no concern here. 
The output is reset to '0' in the following three cases: 
●  After a 1 to 0 transition at input En 
●  When the function was configured for momentary pushbutton action, and one cycle has 
expired since it was switched on 
●  When the position 'Off' was selected at the 'Switch' parameter and confirmed with OK in 
parameter assignment mode 
If retentivity is not set, output Q is initialized after a power failure according to your 
configuration at the "Start" parameter.