LOGO! functions 
 
4.4 Special functions list - SF 
 
LOGO! 
256
 
Manual, 04/2011, A5E03556174-01 
4.4.30 
PI controller 
Short description 
Proportional-action and integral-action controllers. You can use both types of controller 
individually or combined.    
 
Symbol in LOGO! 
Wiring 
Description 
Input A/M 
Set the mode of the controller: 
1: automatic mode 
0: manual mode 
Input R 
Use the input R to reset the output AQ. As long as 
this input is set, the input A/M is disabled.  
Output AQ is set to 0. 
Input PV 
Analog value: process variable, influences the output 
$ᇄ
$4
$0
5
39
3DU
 
Parameter 
SP: Set-value assignment 
 Range of values:  
 -10,000 to +20,000 
KC: Gain 
 Range of values:  
 00.00 to 99.99 
TI: Integral time 
 Range of values:  
 00:01 to 99:59 m 
Dir: Action direction of the controller  
 Range of values:  
 + or - 
Mq: Value from AQ with manual mode 
 Range of values:  
 0 to 1000 
Min: Minimum value for PV 
 Range of values:  
 -10,000 to +20,000 
Max: Maximum value for PV 
 Range of values:  
 -10,000 to +20,000 
A: Gain 
 Range of values:  
 ±10.00 
B: Offset 
 Range of values:  
 ±10,000 
p: Number of decimals 
 Range of values: 
 0, 1, 2, 3