Technical data 
 
A.12 Technical data: LOGO! AM2 RTD 
 
LOGO! 
340
 
Manual, 04/2011, A5E03556174-01 
A.12 
Technical data: LOGO! AM2 RTD 
 
 
LOGO! AM2 RTD 
Power supply 
Input voltage 
12/24 V DC 
Permissible range 
10.8 ... 28.8 V DC 
Power consumption 
30 ... 40 mA 
Voltage failure buffering 
typ. 5 ms 
Power loss at 
• 
12 V 
• 
24 V 
 
• 
0.36 ... 0.48 W 
• 
0.72 ... 0.96 W 
Electrical isolation 
No 
Reverse polarity protection 
Yes 
Ground terminal  
for connecting ground and shielding of the measuring 
line 
Sensor inputs 
Number 
Type 
PT100 or PT1000 with the default temperature 
coefficient of α = 0.003850 for both types, or 
compatible sensors 
Connection of sensors 
• 
2-wire technique 
• 
3-wire technique 
 
• 
Yes 
• 
Yes 
Measurement range 
-50 °C... +200 °C 
-58 °F ... +392 °F 
Settings for the measurement display on 
the LOGO! Basic: 
• 
1 °C steps 
• 
0.25 °C steps 
(rounded to one decimal) 
• 
1 °F steps 
• 
0.25 °F steps 
(rounded to one decimal) 
 
 
• 
Offset: -50, Gain: 0.25 
• 
Offset: -500, Gain: 2.50 
 
• 
Offset: -58, Gain: 0.45 
• 
Offset: -580, Gain: 4.50 
Curve linearization 
No 
Measuring current Ic 
Pulse current signal: 
PT100: 1.141 mA (cycle time = 2.3 ms) 
PT1000: 0.5 mA (cycle time = 2.3 ms) 
Measurement rate 
depends on the installation 
typical: 50 ms 
Resolution 
0.25 °C 
Error limits 
• 
0 °C ... +200 °C 
• 
-50 °C ... 0 °C 
of the final measured value: 
• 
± 2 °C 
• 
± 3 °C 
Electrical isolation 
No