LOGO! installation and wiring 
 
2.4 Putting into operation 
LOGO! 
Manual, 04/2011, A5E03556174-01 
67
 
2.4.3 
Operating states 
LOGO! Base Module operating states 
LOGO! Base Modules (LOGO! Basic or LOGO! Pure) have two operating states: STOP and 
RUN. 
 
STOP 
RUN 
• 
The display shows: 'No Program' (not 
LOGO!...o) 
• 
Switching LOGO! to programming mode 
(not LOGO!...o) 
• 
LED is red 
(only LOGO!...o) 
• 
Display: Screen mask for monitoring I/O and 
messages (after START in the main menu)  
(not LOGO!...o or LOGO!...E) 
• 
Display: Screen mask for monitoring I/O and 
messages (after START in the main menu) or for 
the parameter assignment menu 
 (only LOGO!...E) 
• 
Switching LOGO! to parameter assignment mode
(not LOGO!...o or LOGO!...E) 
• 
LED is green 
(only LOGO!...o) 
Action of LOGO!: 
• 
The input data is not read. 
• 
The circuit program is not executed. 
• 
The relay contacts are permanently open 
or the solid-state outputs are switched off. 
Action of LOGO!: 
• 
LOGO! reads the status of the inputs. 
• 
LOGO! uses the circuit program to calculate the 
status of the outputs. 
• 
LOGO! switches the relay/solid-state outputs on 
or off. 
 
 
 
Note 
After switching the power on, the system briefly switches through the outputs on the LOGO 
24/24o or LOGO! 24C/24Co. With an open circuit, a voltage of > 8 V can occur for up to 
approximately 100 ms; when loaded, this time reduces to a matter of microseconds. 
 
LOGO! expansion modules, operating states   
LOGO! expansion modules have three operating states: The LED (RUN/STOP) is lit green, 
red or orange. 
 
LED (RUN/STOP) is lit 
Green (RUN) 
Red (STOP) 
Orange/Yellow 
The expansion module 
communicates with the device 
to the left. 
The expansion module does not 
communicate with the device to 
its left. 
Initialization phase of the 
expansion module