SPECIFICATIONS - FOR MAGNUM 6K16V FIBER SWITCH 
 
 
Power Supply (Internal, -48VDC Dual-Source, model # Dual-Src-48V) 
 
  DC Power Connector:  First Source: “A+”, “A
-“
, 2nd Source “B
-
“, “B+”  
 
  GND:      Terminal for “earth” or ground wire connection to the hub chassis 
 
  Input:      Two separate sources, each at 36 - 70 VDC  
Power Supply (Internal, 24VDC Dual-Source, model # Dual-Src-24V) 
 
  DC Power Connector:  First Source: “A+”, “A
-“
, 2nd Source “B
-
“, “B+”  
 
  GND:      Terminal for “earth” or ground wire connection to the hub chassis 
 
  Input:      Two separate sources, each at 20 - 36 VDC 
  Power Supply (Internal, 125VDC Dual-Source, model # Dual-Src-125V) 
 
  DC Power Connector:  First Source: “A+”, “A
-“
, 2nd Source “B
-
“, “B+”  
 
  GND:      Terminal for “earth” or ground wire connection to the hub chassis 
 
  Input:      Two separate sources, each at 115 - 150 VDC  
 
   
 
With the exception of the dual DC input power connections and the power 
supply, all specifications and configuration options for the Magnum 6K16V -48VDC, 
24VDC and 125VDC models with this Dual-Source option are identical to those listed in 
the Magnum 6K16V Fiber Switches Installation and User Guide, including Appendix B 
“Internal DC Power Supply Option”  
 
C2.0   
MAGNUM 6K16V, with -48VDC, 24VDC and 125VDC Dual-Source option 
 
The 6K16V-Switch models with the internal -48VDC, 24VDC and 125VDC 
Dual-Source power supply are designed for installations where a battery plant is the 
power source, and where two separate power sources are utilized in order to increase 
operational uptime and to simplify maintenance.  
The functionality of the Magnum 6K16V Switch -48VDC, 24VDC and 
125VDC Dual-Source Option units is identical to the standard AC-powered models.  
Refer to the main sections of this Installation and User Guide for a detailed description 
of the Magnum 6K16V Switches. 
C3.0 
DUAL-SOURCE OPTION, THEORY OF OPERATION 
 
The Dual-Source DC power 
option is designed using diodes inside 
of the chassis on each DC power input 
line. A diode is placed in each of the 
four input lines (behind the four 
external power connection terminals) 
so that power from an external source 
can only flow into the unit.  This allows the unit to operate whenever DC power is 
correctly applied to either or both of the two inputs 
GND
FUSE
+
-
SUPPLY
A+
A-
B-
B+
GND
CHASSIS
HUB
 
 
 
 
54