Magnum DS50 / DS60s Dual Speed Hubs                  Installation and User Guide (06/02)
 
B4.0 INSTALLATION 
 
-36 to -70VDC
_
+
GND
 
This section describes the 
installation of the 24VDC or -48VDC 
power source leads to the 24VDC or -
48VDC power terminal block on the 
Magnum DS50 / DS60. (see figure 
right). 
 
 
Figure B4.1:  Optional Terminal Block on Magnum DS50 / DS60 with -48VDC power 
 
In this picture, the 24VDC or -48VDC terminal block on the Magnum DS50 / DS60 
is located on the rear of the unit and is equipped with three (3) screw-down lead posts. The 
leads are identified as negative (-), positive (+), and chassis ground (GND).  
 
 The actual connection procedure is very straightforward. Simply connect the leads to 
the Magnum unit, beginning with ground.  Ensure that each lead is securely tightened.  
 
Note: The GND should be hooked up first.  The DS50/60  unit has a floating 
ground, so the user may elect to Ground either + or = terminal to suit the customer’s use.   
 
Before connecting hot lines to the Terminal Block of –48VDC or 24VDC,  always 
use a digital voltmeter to measure the output voltage of the power supply and determine the 
lead which is  more “+ve potential”. The more “+ve” voltage lead from 48V  or –48V  supply 
must be connected to the post labeled “+”. 
 
An optional ON-OFF manual switch, available on some Magnum units, is not 
included on the Magnum DS50 / DS60 Dual-speed Hubs Plus.
 
B4.1   
UL Requirements 
1.   Minimum 14 AWG cable for connection to a Centralized DC power source. 
2.   Fastening torque of the lugs on the terminal block:  9 inch pound max. 
3.   Centralized DC Power Source cable securement, use at least four cable ties to secure 
the cable to the rack at least 4 inches apart with the first one located within 6 inches 
of the terminal block.
 
B5.0 OPERATION 
 
Operation of the Magnum DS50 / DS60 with the optional 24VDC or -48VDC power 
supply is identical to that of the standard AC-powered models.   
B6.0 ORDERING 
INFORMATION 
 
To order the optional -48VDC power supply factory installed, add a suffix of “--
48VDC” after the product’s standard model #.  Example: Magnum DS50-48VDC. 
 
Similarly, to order the optional 24VDC industrial specific power supply factory 
installed, add a suffix of “ 24VDC” after the product ‘s standard model #.  
 Example: Magnum DS60- 24VDC.  
 
B7.0 TROUBLESHOOTING 
 
Please refer to Section 6.0 for troubleshooting 
 