Note: Before connecting to Terminal Block of –48VDC, 24VDC or 125VDC,
always use a digital voltmeter to measure the output voltage of the power supply and
determine the lead which is  more  “+ve potential Lead”. The more “+ve” voltage
terminal lead from 48V  or –48V Power supply must be connected to the post labeled
“+”.
The GND can be hooked at the last.
Disconnecting the DC power source is used to remove the unit from service, and as a
power-down to RESET the hub’s electronics if needed.
B4.1  
UL Requirements
1.   Minimum 14 AWG cable for connection to a Centralized DC power source.
2.   Fastening torque of the lugs on the terminal block:  9 inch pound max.
3.   Centralized DC Power Source cable securement, use at least four cable ties to
secure the cable to the rack at least 4 inches apart with the first one located
within 6 inches of the terminal block.
B5.0
OPERATION
Operation of the Magnum 1000’s with the optional -48VDC, 24VDC &
125VDC power supply is identical to that of the standard AC-powered models.  
B6.0
ORDERING INFORMATION
To order the optional -48VDC power supply factory installed, add a suffix of
“-48VDC” after the product’s standard model #.  Example:  
Magnum 1016-48VDC. 
 Similarly for “24VDC”
: Magnum 1016-24VDC.
B7.0
TROUBLESHOOTING
Please refer to Section 6.0 for troubleshooting