Magnum DS880 Dual-Speed Stackable Hubs                  Installation and User Guide (05/01)  
 
27 
www  GarrettCom  com
.
.
B4.0 INSTALLATION 
 
 
This section describes the installation of the 48 VDC power source leads to the 48 
VDC power terminal block on the Magnum DS880s. (see figure below). 
 
 
Figure B4.1:  48 VDC Terminal Block 
on Magnum DS880-48VDC 
 
 
 
 
The 48 VDC terminal block on 
the Magnum DS880s is located on the rear 
of the unit and is equipped with three (3) 
screw-down lead posts.  The leads are 
identified as negative (-), positive (+), and chassis ground (GND).  The actual connection 
procedure is very straightforward. To avoid  the confusion  of -48V or +48V  power supply, 
use a digital voltmeter to measure the output voltage and figure out the +VE Lead. The 
more +VE voltage  terminal  lead  from the +48V or-48V  power supply should be 
connected to the post leveled “+”  and then the rest.  Ensure that each lead is securely 
tightened
36-70VDC
_
+
GND
ON
OFF
 
 
On the premium-priced NEBS-compliant Magnum DS880-48V models, an ON-OFF 
switch is included, located in the rear at the power input.  This can be used in conjunction with 
power connections, and as a RESET for the hub’s electronics. 
 
B4.1   
UL Requirements 
1.   Minimum 14 AWG cable for connection to a Centralized DC power source. 
2.   Fastening torque of the lugs on the terminal block:  9 inch pound max. 
3.   Centralized DC Power Source cable securement, use at least four cable ties to secure 
the cable to the rack at least 4 inches apart with the first one located within 6 inches 
of the terminal block.
 
 
B5.0 OPERATION 
 
Operation of the Magnum DS880s with the optional 48VDC power supply is identical 
to that of the standard AC-powered models.   
 
B6.0 TROUBLESHOOTING 
 
Please refer to Section 5.0  for troubleshooting