Meridian America 21 Manual De Usuario
Operating power requirements 37
Module power consumption
The typical and worst case power consumption data for each fully configured
module are shown in Table 14.
The “typical power” data is generally adequate for use in
power
engineering calculations, since it is representative of most systems with
Modules fully loaded (configured) with cards, and under moderate traffic
conditions.
Modules fully loaded (configured) with cards, and under moderate traffic
conditions.
The “maximum power” dam is shown for reference and planning purposes
when needed, and was calculated for each module based on a fully-loaded
card cage, in the worst-possible operational configuration (in terms of power
consumption), with each card consuming typical power, plus 10% added
margin. For example, the maximum power consumption for the
Intelligent Peripheral Equipment Module was based on a configuration of
sixteen
margin. For example, the maximum power consumption for the
Intelligent Peripheral Equipment Module was based on a configuration of
sixteen
Universal Trunk cards, all under 100% traffic conditions,
along with a Controller card and additional power margin.
. .
Table 14
SL-1 System UEM power consumption
SL-1 System UEM power consumption
Power consumptbn (Watts)
Module
Typical
Maximum
400
4 2 0
Meridian Mail
400
450
Common/Peripheral Equip.
5 0 0
6 9 0
Peripheral Equipment
400
575
CPU
300
335
Network
300
325
Junctor
0
0
Peripheral Equipment
550
720
Remote Peripheral Equipment
300
350
Pedestal (Blowers)
5 0
80
Power engineering 553-3001-152