Meridian America 21 Manual De Usuario

Descargar
Página de 867
Operating power requirements 37
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Module power consumption
The typical and worst case power consumption data for each fully configured
module are shown in Table 14.
The “typical power” data is generally adequate for use in 
 power
engineering calculations, since it is representative of most systems with
Modules fully loaded (configured) with cards, and under moderate traffic
conditions.
The “maximum power” dam is shown for reference and planning purposes
when needed, and was calculated for each module based on a fully-loaded
card cage, in the worst-possible operational configuration (in terms of power
consumption), with each card consuming typical power, plus 10% added
margin. For example, the maximum power consumption for the 
Intelligent Peripheral Equipment Module was based on a configuration of
sixteen 
 Universal Trunk cards, all under 100% traffic conditions,
along with a Controller card and additional power margin.
. .
Table 14
SL-1 System UEM power consumption
Power consumptbn (Watts)
Module
Typical
Maximum
 
400
4 2 0  
 Meridian Mail
400
450
 Common/Peripheral Equip.
5 0 0
6 9 0
 Peripheral Equipment
400
575
 CPU
300
335
 Network
300
325
 Junctor
0
0
 Peripheral Equipment
550
720
 Remote Peripheral Equipment
300
350
Pedestal (Blowers)
5 0
80
Power engineering 553-3001-152