Delta Electronics RTU-EN01 Manual De Usuario

Descargar
Página de 52
Modbus TCP Remote I/O Communication Module RTU-EN01 
DVP-PLC Operation Manual 
15
R# 
Attribute
Content 
Explanation 
Default 
Latched 
R/W 
RTC 6 
Real-time clock
 
OFF NO 
R/W 
RTC 7 
Real-time clock
 
OFF NO 
R/W 
RTC 8 
Real-time clock
 
OFF NO 
R/W 
RTC 9 
Real-time clock
 
OFF NO 
10 
R/W 
RTC 10 
Real-time clock
 
OFF NO 
11 
R/W 
RTC 11 
Real-time clock
 
OFF NO 
12 
R/W 
RTC 12 
Real-time clock
 
OFF NO 
13 
R/W 
RTC 13 
Real-time clock
 
OFF NO 
14 
R/W 
RTC 14 
Real-time clock
 
OFF NO 
15 
R/W 
RTC 15 
Real-time clock
 
OFF NO 
Symbol “R” refers to ready only; “R/W” refers to read and write. 
 
R # 0 :   R T C   0
 
Explanations: 
When the RTC function is enabled, and the assigned trigger condition is true, RTU-EN01 will set the bit device R0 
to ON and continue to output or stop according to the set time. 
 
R # 1   ~   # 1 5 :   R T C   1   ~   1 5
 
Explanations: 
Please refer to R#0. 
 
5 Modbus 
Communication 
5.1  Function Codes Supported 
Function code 
Explanation 
Devices supported 
0x02 
Read digital input point 
RX, RY, T, R, C 
0x03 
Read register 
BR, T, C, RCR 
0x05 
Write single bit device 
RY, T, R, C 
0x06 
Write single register 
BR, T, C, RCR 
0x0F 
Write multiple bit devices 
RY, T, R, C 
0x10 
Write multiple registers 
BR, T, C, RCR 
0x17 
Read/write multiple registers 
BR, T, C, RCR 
5.2  Exception Codes Supported 
Exception code 
Explanation 
0x01 Illegal 
function 
0x02 
Illegal data address 
0x03 
Illegal data value 
0x04 Slave 
device 
failure 
0x0b 
Gateway target device failed to respond.