Modbus TCP Remote I/O Communication Module RTU-EN01 
 
DVP-PLC Operation Manual 
42 
7  Application Examples – DCISoft 
7.15 Smart PLC: IF-THEN 
Application  Setting up IF-THEN in Smart PLC functions by using DCISoft. 
Steps 
1.  When RX#0 and RX#1 are ON, set RY0 to output. 
2.  When RX#2 turns from OFF to ON, set RY1 to reversing its direction. 
 
1.  See the connection method (as below) and 6.1 for how to set up communication. 
D
V
P
-0
2
D
A
D
V
P
-0
8
S
T
D
V
P
-1
6S
P
D
V
P
-0
4
A
D
D
V
P
-0
4
T
C
D
V
P
-0
4
P
T
Ethernet
RTU-EN01
DI/DO
AI/AO
COM2
R
T
U
-E
N
0
1
PC
 
2.  Open the setup page and switch to “Smart PLC” page. 
3.  Select “RX 0 On” and “RX 1 On” in the IF column and select “AND” for the relation between conditions. 
Next, select “RY 0 Set” in the THEN column and press “Add” to add the settings into the table below. 
 
4.  Select “RX 2 Rising” in the IF column and “RY 1 Toggle” in the THEN column. Press “Add” to add the 
settings into the table below. Press “Apply” to store these settings into RTU-EN01.