Warning
 
 
This instruction sheet provides only information on the electrical specification, general functions, installation and 
wiring. The program design and applicable instructions for DVP-EC3 are the same as those applicable for DVP-ES 
series. For detailed information, please refer to “DVP-PLC Application Manual: Programming”. For details of the 
optional peripheral, please refer to the instruction sheet enclosed in it. 
 
DVP-EC3 series PLC is an OPEN TYPE device and therefore should be installed in an enclosure free of airborne 
dust, humidity, electric shock and vibration. The enclosure should prevent non-maintenance staff from operating the 
device (e.g. key or specific tools are required for operating the enclosure) in case danger and damage on the device 
may occur. 
 
DO NOT connect the input AC power supply to any of the I/O terminals; otherwise serious damage may occur. Check 
all the wiring again before switching on the power. Make sure the ground terminal 
  is correctly grounded in order 
to prevent electromagnetic interference. 
 Introduction 
Thank you for choosing Delta DVP-EC3 series programmable logic controller. DVP-EC3 currently offers 10-16 
I/O points. To ensure proper installation, operation and maintenance, please read this instruction sheet carefully 
and provide users with this instruction sheet before installing DVP-EC3. 
 Product Profile & Outline 
+24 V24 G S/ S X 0 X 1 X 2 X3 X 4 X5 X 6 X 7
L
N
C 0 Y0 Y1 Y 2 Y 3 C 1 Y 4 Y 5
POWE R
R UN
ER ROR
DVP1 6EC
8DI-DC  /  8DO-R
D ir ec t m oun ting ho l e
Inpu t po ints Ind i c atio n
D C p ow e r s u pp l y o u tpu t
I/O p oin t in di ca to rs
C OM 1 C om mu n i ca tion
(RS-23 2C)
por t 
D IN r ai l (35m m)
D ir ec t m ou ntin g ho l e
F ix ed I/O te r min als
D IN rai l c li p
 
P OW ER , R U N & ER RO R i n dic a tors
O utp ut poi nts In d ic a tio n
A C p ow e r s u pp l y in put
C OM 2 C om mun i ca ti on
(RS- 48 5 )
p ort 
D + D - S G
Y 6 Y 7
M od el n a me
COM2
COM1
 
 Dimensions 
9 0.5 m m
95 m m
4 8.5 m m
90m m
99 m m
+24V 24G S/S X0 X1
X2 X3
X4 X5 X6 X7
IN
OUT
PO WE R
R U N
E R RO R
L
N
C0
Y0 Y1 Y2
Y3 C1 Y4
Y5
DVP16EC
8DI-DC / 8DO-R
I NP U T
A C  1 00 ~2 4 0V
0 1 2 3 4 5 6 7
0 1 2 3 4 5 6 7
D+ D- SG
Y6 Y7
C OM2
C OM1
 
ENGLISH 
 Specifications 
 
 
Model 
  Item 
DVP10EC00
□3 
DVP14EC00
□3 
DVP16EC00
□3 
Power supply voltage 
100 ~ 240V AC (-15% ~ 10%), 50/60Hz ± 5% 
Operation 
DVP-EC3 starts to run when the power supply rises to 95 ~ 100V AC and stops 
when the power supply drops to 70V AC. It continues to run for 10ms after the 
power supply is cut off. 
Power supply fuse   
2A/250V AC 
Power consumption 
9VA 
DC24V Supply Current 
100mA 
Power supply protection 
DC24V output short circuit protection 
Voltage withstand 
1,500V AC (Primary-secondary), 1,500V AC (Primary-PE), 500V AC 
(Secondary-PE) 
Insulation resistance 
> 5MΩ at 500V DC (between all I/O points and earth) 
Noise immunity 
ESD: 8KV Air Discharge 
EFT: Power Line: 2KV, Digital I/O: 1KV, Analog & Communication I/O: 250V 
RS: 26MHz ~ 1GHz, 10V/m 
Earth 
The diameter of grounding wire shall not be less than that of L, N terminal of the 
power supply. (When many PLCs are in use at the same time, please make sure 
every PLC is properly grounded.) 
Operation/storage 
Operation: 0°C ~ 55°C (temperature), 50 ~ 95% (humidity), Pollution degree2 
Storage: -25°C ~ 70°C (temperature), 5 ~ 95% (humidity) 
Vibration/shock 
resistance 
International standards: IEC61131-2, IEC 68-2-6 (TEST Fc)/ IEC61131-2 & IEC 
68-2-27 (TEST Ea) 
RS-485 communication 
mode 
Not supported 
Not supported 
Supported 
Weight (g) 
R: 192g; T: 180g 
R: 202g; T: 185g 
R: 212g; T: 190g 
 
Input Point 
Input point type 
Digital Input 
Input type 
DC (SINK or SOURCE) 
Input current 
24V DC 5mA 
Off → On, > 15V DC 
Action level 
On → Off, < 5V DC 
Reaction time 
(Conversion sampling 
time) 
Approx. 10ms (0 ~ 20ms adjustable in D1020) 
 
Output Point 
Output point type 
Relay-R 
Transistor-T 
Current specification 
2A/1 point (5A/COM) 
0.5A/1 point (2A/COM) 
Voltage specification 
< 250V AC, 30V DC 
5 ~ 30V DC 
(UP, ZP must work wit external 
auxiliary power supply 24V DC -15% 
~ +20%, rated consumption  approx. 
1mA/point) 
75VA (inductive) 
Maximum load 
90W (resistive) 
15W/1 point (Resistive) 
Reaction time 
Approx .10ms 
Off 
→  On 30us, On  →  Off 100us 
 Installation & Wiring 
3.1    I/O Terminal Layout 
◎  DVP10EC00R3/T3 
X4
X3
X2
X1
X0
S/S
24G
+24V
X5
Y3
Y2
Y1
Y0
C0
D VP 10EC 00R3 (6DI -DC / 4D O- R)
 
X4
X3
X2
X1
X0
S/S
24G
+24V
X5
Y3
Y2
Y1
Y0
ZP
UP
DVP10EC00 T3 (6DI- DC / 4DO- T)
 
◎  DVP14EC00R3/T3 
X4
X3
X2
X1
X0
S/S
24G
+24V
X7
X6
X5
Y4
C1
Y3
Y2
Y1
Y0
C0
Y5
DVP14EC00R3 (8DI- DC / 6DO-R)
   
X4
X3
X2
X1
X0
S/S
24G
+24V
X7
X6
X5
Y4
Y3
Y2
Y1
Y0
ZP
UP
Y5
D VP14EC 00T3 (8DI- DC / 6DO-T)
 
◎  DVP16EC00R3/T3 
X4
X3
X2
X1
X0
S/S
24G
+24V
X7
X6
X5
Y4
C1
Y3
Y2
Y1
Y0
C0
Y5
DVP16EC00R3 (8DI-DC / 8DO-R)
Y6
Y7
SG
D-
D+
   
X4
X3
X2
X1
X0
S/S
24G
+24V
X7
X6
X5
Y4
Y3
Y2
Y1
Y0
ZP
UP
Y5
DVP16EC00T3 (8DI-DC / 8DO- R)
Y6
Y7
SG
D-
D+
 
1.  Use the 12-24 AWG single-core bare wire or the multi-core wire for the I/O wiring, and please use 60/75°C 
copper conductor only. The twisting power of the screw for the DVP-EC3 terminal is 3.80 kg-cm (3.30 
lb-in) . 
2.  DO NOT wire empty terminal. DO NOT place the input signal wire and output power wire in the same 
wiring circuit. 
3.  DO NOT drop tiny metallic conductor into DVP-EC3 while screwing and wiring 
3.2    Mounting & Installation 
Please install PLC in an enclosure with sufficient space around it to allow heat dissipation. For heat 
dissipation, make sure to provide a minimum clearance of 50mm between the unit and all sides of the cabinet. 
(See the figure.) 
 
How to screw: Please use M4 screw according to the dimension of the product. 
How to install DIN rail: PLC can be secured to a cabinet by using the 35mm DIN rail. When mounting PLC to 
DIN rail, be sure to use the end bracket to stop any side-to-side movement of it and reduce the change of 
wires being loosen. A small retaining clip is at the bottom of it. To secure PLC to DIN rail, place the clip onto 
the rail and gently push it up. To remove it, pull the retaining clip down and gently remove it from DIN rail.
 
3.3    Wiring Notes 
 Specification & Wiring of Power Supply 
The power supply input for DVP-EC3 model is AC input. When operating DVP-EC3, please make sure that: 
1.  The input voltage should be 100 ~ 240VAC. The power supply should be connected to L and N terminals. 
Please note that wiring AC110V or AC220V to +24V output terminal or digital input points will result in 
serious damage on it. 
2.  Use 1.6mm wire (or longer) for the grounding of it. 
3.  The power shutdown of less than 10ms will not affect the operation of it. However, power shutdown time 
that is too long or the drop of power supply voltage will stop the running of it, and all outputs will go “OFF”. 
When the power supply turns normal again, DVP-EC3 will automatically return to its operation. (Please be 
aware of the latched auxiliary relays and registers inside DVP-EC3 when programming.) 
4.  For max. output of the +24V power supply output terminal for each model, please refer to the electrical 
specification table. DO NOT connect other external power supplies to this terminal. Every input point 
requires 5 ~ 7mA to drive (e.g. 16 input points will require 80 ~ 112mA to drive). The +24V input on DVP- 
EC3 is only for digital input points; other external loads are not suggested. 
L
100~240VAC
N
24G S/S
X0
X1
X2
2. 0A
DC/DC
5V
+2 4V
 
 Safety Wiring 
Since DVP-EC3 controls many devices, actions of any device may affect actions of other devices, and the 
breakdown of any one device may cause the breakdown of the entire auto-control system and danger. 
Therefore, we suggest you wire a protection circuit at the power supply input terminal, as shown in the figure 
below. 
1  
AC power supply load 
2  
Power supply circuit protection fuse (3A) 
3  
POWER indicator 
4  
Emergency stop: This button can cut off the system 
power supply when accidental emergency takes place 
5  
Breaker 
6  
DVP-EC3 (main processing unit) 
7  
Earth resistance: < 100Ω 
 
8  
Power supply: 100 ~ 240V AC, 50/60Hz 
 
 I/O Point  Wiring 
The input signal of the input point is the DC power DC input. There are two types of DC type wiring: SINK and 
SOURCE, defined as follows: 
◎  Input Point Loop Equivalent Circuit & Wiring 
DC Signal IN 
(SINK mode)
 
+24 V
24 G
S/ S
X0
+5 V
24V D C
X1
 
DC Signal IN 
  (
SOURCE mode)
 
+24V
24G
S/S
X0
+5V
24VDC
X1
 
Below is an example. For detailed point configuration, please refer to specifications of each model: 
◎  Relay (R) Output Circuit Wiring 
1  
Flywheel diode: To extend the life span of contact 
2  
Emergency stop: Uses external switch 
3  
Fuse: Uses 5 ~ 10A fuse at the shared terminal of 
output contacts to protect the output circuit   
4  
Varistor: To reduce the interference on AC load 
5  
Empty terminal: Not in use 
6  
DC power supply 
7  
Neon indicator 
8  
AC power supply 
9  
Incandescent light (resistive load) 
 
10  
Manually exclusive output: Uses external circuit and 
forms an interlock, together with DVP-EC3 internal 
program, to ensure safety protection in case of any 
unexpected  errors.   
◎  Transistor (T) Output Circuit Wiring 
1  
DC power supply 
2  
Emergency  stop 
3  
Circuit protection fuse 
4  
The output of the transistor model is “open 
collector”. If Y0/Y1 is set to pulse output, the output 
current has to be 0.05 ~ 0.5A to ensure normal 
operation of the model. 
 
5  
Manually exclusive output: Uses external circuit and 
forms an interlock, together with DVP-EC3 internal 
program, to ensure safety protection in case of any 
unexpected  errors. 
 
 
注意事項 
 
本使用說明書提供給使用者電氣規格、功能規格、安裝配線之相關注意事項。其他詳細之程式設計及指令與
DVP-ES
系列相容,詳細說明請見 DVP-PLC 應用技術手冊【程式篇】,選購之周邊裝置詳細說明請見該產品
隨機使用說明書。 
 
本機為開放型  (OPEN TYPE)  機殼,因此使用者使用本機時,必須將之安裝於具防塵、防潮及免於電擊∕衝
擊意外之外殼配線箱內。另必須具備保護措施(如:特殊之工具或鑰匙才可打開)防止非維護人員操作或意
外衝擊本體,造成危險及損壞。 
 
交流輸入電源不可連接於輸入∕出信號端,否則可能造成嚴重損壞,請在上電之前再次確認電源配線。請勿
在上電時觸摸任何端子。本體上之接地端子    務必正確的接地,可提高產品抗雜訊能力。 
 產品簡介 
感謝您採用台達 DVP-EC3 系列可程式控制器。DVP-EC3 系列目前提供 10 ~ 16 點數的主機。為了確保能夠正確
地安裝及操作可程式邏輯控制器,請在裝機之前,詳細閱讀本使用手冊,並請妥善保存及交由該機器的使用者。
 
  產品外觀及各部介紹 
直接 固定孔
固定 式輸 出 /  端 子
  入
C O M 1 
程 式通訊口
輸 入 /  出 點指示燈
  輸
直接固定 孔
電源、運行及錯 誤指 示燈
直流電源 輸出
輸出點指 標
交流電源 輸入
輸入 點指 標
+24V 24G S/ S X0 X1 X2 X3 X4 X5 X6 X7
L
N
C0 Y0 Y1 Y2 Y3 C1 Y4 Y5
POWE R
RUN
ERROR
D VP1 6EC
8DI-DC / 8DO-R
D IN 
( 3 5 mm )
軌槽 
( RS - 2 32 C )
D IN  
軌固 定扣
C O M 2 
通 訊口(RS-48 5)
D+ D- SG
Y6 Y7
機種 型號
C O M1
C O M2
 
  尺寸規格 
9 0.5 m m
95 m m
4 8.5 m m
90m m
99 m m
+24V 24G S/S X0
X1
X2 X3
X4
X5 X6 X7
IN
OUT
PO WE R
R U N
E R RO R
L
N
C0
Y0 Y1 Y2 Y3 C1 Y4
Y5
DVP16EC
8DI-DC / 8DO-R
I NP U T
A C  1 00 ~2 4 0V
0 1 2 3 4 5 6 7
0 1 2 3 4 5 6 7
D+ D- SG
Y6
Y7
C OM2
C OM1
 
繁體中文 
  電氣規格 
 
機種 
項目 
DVP10EC00
□3 
DVP14EC00
□3 
DVP16EC00
□3 
電源電壓 
100 ~ 240V AC (-15% ~ 10%), 50/60Hz ± 5% 
動作規格 
當電源緩升至 95 ~ 100V    AC 時,DVP-EC3 開始動作,當電源緩降至 70V AC 時,DVP-EC3
會停止動作。電源瞬間斷電 10ms 以內繼續運行。 
電源保險絲容量 
2A/250V AC 
消耗電力 
9VA 
DC24V
供應電流  100mA 
電源保護 
DC24V
輸出具短路保護 
突波電壓耐受量 
1,500V AC (Primary-secondary) 
1,500V AC (Primary-PE) 
500V AC (Secondary-PE) 
絕緣阻抗 
5MΩ
以上(所有輸出/入點對地之間 500V DC) 
雜訊免疫力 
ESD: 8KV Air Discharge 
EFT: Power Line: 2KV, Digital I/O: 1KV, Analog & Communication I/O: 250V 
RS: 26MHz ~ 1GHz, 10V/m 
接地 
接地配線之線徑不得小於電源端 L, N 之線徑(多台 PLC 同時使用時,請務必單點接地) 
操作/儲存環境 
操作:0°C ~ 55°C(溫度),50 ~ 95%(濕度)污染等級  2 
儲存:-25°C ~ 70°C  (溫度),5 ~ 95%(濕度) 
耐振動/衝擊   
國際標準規範  IEC61131-2, IEC 68-2-6 (TEST Fc)/IEC61131-2 & IEC 68-2-27 (TEST Ea) 
RS-485
通訊模式 
不支援 
不支援 
支援 
重量(約,g) 
R
:192g;T:180g 
R
:202g;T:185g 
R
:212g;T:190g 
 
輸  入  點  電  氣  規  格 
輸入點類型 
數位輸入 
輸入形式 
直流(SINK 或 SOURCE) 
輸入電流 
24VDC
,5mA 
Off → On
,15V DC 以上 
動作位準 
On → Off
,5V DC 以下 
反應時間 
(轉換取樣時間) 
約 10ms(由 D1020 及可作 0 ~ 20ms 的調整) 
 
輸  出  點  電  氣  規  格 
輸出點形式 
繼電器-R 
電晶體-T 
電流規格 
2A/1
點(5A/COM) 
0.5A/1
點(2A/COM) 
電壓規格 
250V AC, 30V DC
以下 
5~30VDC 
(UP, ZP
必須外加輔助電源 24V DC -15% ~ +20% 
額定消耗約 1mA/點) 
75VA
(電感性) 
最大負載 
90W
(電阻性) 
15W/1
點(電阻性) 
反應時間 
約 10ms 
Off → On 30us
,On → Off 100us