Warning 
  Always read this instruction sheet thoroughly before using DVP EH digital I/O extension unit. 
  This is an OPEN TYPE extension unit. The extension unit should be kept in an enclosure away from airborne, dust, 
high humidity, electric shock risk and vibration. Also, it is equipped with protective methods such as special tools or 
keys to open the enclosure, so as to avoid the hazard to users and damage the extension unit. 
  DO NOT connect AC main circuit power supply to any of the input/output terminals, as it will damage the extension 
unit. Check all the wiring prior to power up. DO NOT touch terminals when power on. 
 Introduction
 
Thank you for choosing Delta DVP-EH series PLC. The main processing units offer 8 ~ 48 points and the 
maximum input/output can be extended up to 256 points. 
 Product Profile and Outline 
1
3
4
3
5
5
2
7
7
 
2
1
5
5
3
3
4
7
7
 
 
Dimension  (mm) 
Model   
Length 
Width 
Height 
DVP08HM11N 
90 
40 
82 
DVP16HM11N 
90 
55 
82 
DVP08HN11R/T 
90 
40 
82 
DVP16HP11R/T 
90 
55 
82 
 
3
4
2
6
6
6
7
7
3
3
8
 9
1
10
11
 
 
Dimension  (mm) 
Model 
Length 
Width 
Height 
DVP32HN00R/T 
90 
143.5 
82.2 
DVP32HP00R/T 
90 
143.5 
82.2 
DVP48HP00R/T 
90 
174 
82.2 
 
1. Power, low voltage indicators 
5.  Extension  wiring 
9. Cover 
2.  I/O  terminals 
6.  Extension port cover 
10. Input  indicators 
3. DIN rail clip 
7.  Direct  mounting  holes   
11.  Output  indicators 
4. DIN rail 
8. Model name 
 
 DVP EH Series Model 
 
Input unit 
Output unit 
Model 
Power 
Points 
Type 
Points 
Type 
DVP08HM11N 
DVP16HM11N 
16 
N/A 
DVP08HN11R 
DVP08HP11R 
DVP16HP11R 
Relay: 250V AC/30V DC 2A/1point 
DVP08HN11T 
DVP08HP11T 
DVP16HP11T 
24V DC 
DC Type 
Sink/Source 
Transistor: 5 ~ 30V DC 0.3A/1point at 40°C 
ENGLISH 
 Specifications 
 Electrical Specification 
 
Model   
  Item 
08HM11N 
16HM11N 
08HN11R/T  08HP11R/T  16HP11R/T  32HN00R/T 
32HP00R/T 
48HP00R/T 
Power supply voltage 
24V DC (20.4 ~ 28.8V DC) (-15% ~ 20%) 
100~240V AC (-15%~10%), 50/60Hz ± 5% 
Power consumption 
1W/1.5W 
1.5W 
1.5W 
2W 
30VA 
30VA 
30VA 
24V DC supply current 
NA 
NA 
NA 
NA 
NA 
500mA 
500mA 
Power protection 
24V DC output  with  short-circuit  protection 
Voltage withstand 
1,500V AC (Primary-secondary), 1,500V AC (Primary-PE), 500V AC (Secondary-PE) 
Insulation  resistance 
> 5 MΩ at 500V DC (Between all input/output and earth) 
Noise  immunity 
ESD: 8KV Air  Discharge, EFT: Power Line: 2KV, Digital I/O: 1KV, Analog & 
Communication  I/O:  250V,   
Digital I/O: 1KV, RS: 26MHz ~ 1GHz, 10V/m 
Grounding 
The diameter of grounding wire cannot be smaller than the wire diameter of the terminals Land 
N (All DVP units should be grounded directly to the ground pole.) 
Environment 
Operation:  0
°C ~ 55°C (temperature),  50 ~ 95% (humidity), Pollution degree 2;   
Storage: -25
°C ~ 70°C (temperature),  5 ~ 95% (humidity) 
Vibration/shock 
resistance 
Standard: IEC61131-2, IEC 68-2-6 (TEST Fc)/IEC61131-2 & IEC 68-2-27 (TEST Ea) 
Weight  (g) 
124/160 
130/120 
136/116 
225/210 
660/590 
438/398 
616/576 
Approvals 
 
 
 
 
 I/O Terminal Specification 
Input point 
Input  point type 
DC 
Input  type 
DC (SINK or SOURCE) 
Input  current 
24V DC 5mA 
Off
→On, above 16.5V DC     
Active  level 
On
→Off, below 8V DC 
Reaction time 
About 20ms 
Circuit isolation 
/operation  indicator 
Photocoupler/LED On 
 
Output  point 
  Output point type 
  Relay-R 
  Transistor-T 
Current specification 
1.5A/1point (5A/COM) 
55°C 0.1A/1point, 50°C 0.15A/1point, 
45°C 0.2A/1point, 40°C 0.3A/1point (2A/COM) 
Voltage specification 
Below 250V AC, 30V DC 
30V DC 
75VA (inductive) 
Maximum  load 
90W (resistive) 
9W 
Reaction  time 
About 10ms 
Off
→On 15us    On→Off 25us 
Input unit 
Output unit 
Model 
Power 
Points 
Type 
Points 
Type 
DVP32HN00R 
32 
DVP32HP00R 
16 
16 
DVP48HP00R 
24 
24 
Relay: 250V AC/30V DC 2A/1point 
DVP32HN00T 
32 
DVP32HP00T 
16 
16 
DVP48HP00T 
100 ~ 240V   
AC 
24 
DC Type 
Sink/Source 
24 
Transistor:  5 ~ 30V DC 0.3A/1 point at 40°C 
 Installation and Wiring 
 Digital I/O Terminal Wiring 
08HM 
DVP-08HM (8in)
X0 X
2
X
4 X6
X
1 X3
X
5 X7
S/S
 
08HN 
DVP-08HN (8out)
Y0 Y1
Y3
Y4 Y5
Y7
C0 Y2
C1 Y6
 
08HP 
DVP-08HP (4in/4out)
X 0
Y1
Y 3
C0 Y2
Y0
X 2
S /S X 1 X3
 
16HM 
DVP-16HM (16in)
X10 X 11
S /S
X1
X 3
S/S
X12 X13 X 14 X15 X16 X 17
X 0
X2
X4 X5
X7
X6
 
16HP 
DVP-16HP (8in/8out)
X4 X5
X 1
X3
S /S
X6 X7
Y3
Y4 Y5 Y 6
X0
X 2
C 0 Y 0
Y2
Y 1
Y 7
 
32HN 
X15
X14
C3
Y12
Y11
Y10
Y7
Y6
C2
Y5
Y4
Y3
C1
Y2
Y1
Y16
Y20
Y21 Y22 Y23
Y24
C7
C6
C5
C4
Y25
Y30
Y31
Y35
Y36
Y34
Y32
Y27
Y26
C0
DVP-32HN(32out)
(AC Power IN)
Y33
Y37
 
32HP 
X1 7
X16
X15
X14
X13
X12
X11
X1 0
X7
X6
X5
X4
X3
X2
X1
X0
Y0
Y1
Y2
Y3
Y4
Y5
Y6
C3
C2
C1
C0
Y7
Y1 2
Y13
Y16
Y17
Y1 5
Y1 4
Y11
Y1 0
S/S
DVP-32HP(16in/16out)
(AC Power IN,DC Signal IN)
 
48HP 
X17
X16
X15
X14
X13
X12
X11
X10
X7
X6
X5
X4
X3
X2
X1
X0
Y0
Y1
Y2
Y3
Y4
Y5
Y6
C3
C2
C1
C0
Y7
Y12
Y13
Y16
Y17
Y15
Y14
Y11
Y10
S/S
X27
X26
X25
X24
X23
X22
X21
X20
C4 Y21
Y22
Y27
Y23
Y26
Y24
Y20
Y25
DVP-48HP(24in/24out)
(AC Power IN,DC Signal IN)
 
 Mounting Arrangements and Wiring Notes 
DIN Rail Installation: 
The DVP-PLC can be secured to a cabinet by using the DIN 
rail that is 35mm high with a depth of 7.5mm. When 
mounting the PLC on the DIN rail, be sure to use the end 
bracket to stop any side-to-side motion of the PLC, thus to 
reduce the chance of the wires being pulled loose. On the 
bottom of the PLC is a small retaining clip. To secure the 
PLC to the DIN rail, place it onto the rail and gently push up 
on the clip. To remove it, pull down on the retaining clip and 
gently pull the PLC away from the DIN rail. Please see the 
figure on the right: 
 
Direct Mounting: Use the specified dimensions and install with M4 screws. 
For heat dissipation. Make 
sure to provide a minimum 
clearance of 50mm between 
the unit and all sides of the 
cabinet. (shown as below) 
D V P MP U
  >  5 0 mm
  >  5 0mm
> 5 0 mm
> 5 0 mm
 
Wiring: 
Below 6.2
To suit M3.5 screw terminal
Below 6.2
 
1. Please use O-type or Y-type terminals for I/O wiring terminals. The 
specification for the terminals is as shown on the left. PLC terminal screws 
should be tightened to between 5 ~ 8 kg-cm (4.3 ~ 6.9 in-lbs). Use copper 
conductor only, 60°C/75°C. 
2.  DO NOT wire to the No Function terminals   
•  . I/O signal wires or power 
supply should not run through the same multi-wire cable or conduit. 
3. When tightening the screws and performing wiring, please avoid that 
metallic particles fall into PLC. After completing wiring, please remove the 
label which is used to obstruct the metallic particles on the ventilation hole 
for well heat dissipation. 
4.  There should be a 50mm or more distance between the PLC and other 
control component. Also, keep the PLC away from high voltage line and 
power equipment.
 
Environment: 
1.
 DO NOT store the PLC in an airborne dust, smoky, metallic particles, corrosive or flammable gases. 
2. DO NOT store the PLC in a location where temperatures and humidity will exceed specification. 
3. DO NOT mount the PLC in a location where vibration and shock will exceed specification. 
 I/O Point Serial Sequence 
When connecting MPU with less than 32 points to extension unit, the input number of 1
st
 extension unit is 
started from X20 in sequence and the output number is started from Y20 in sequence. If connecting MPU with 
more than 32 points to extension unit, the input number of the 1
st
 extension unit is started from the last input   
number of the MPU in sequence and the output number is started form the last output number of the MPU in 
sequence. 
MP U
EXT 1 EXT 2 EXT3 EXT 4
 
PLC 
Model 
Input 
points 
Output   
points 
Input number 
Output number 
MPU  16EH/32EH/64EH  8/16/32 
8/16/32  X0~X7/X0~X17/X0~X37 
Y0~Y7/Y0~Y17/Y0~Y37 
EXT1 
32HP 
16 
16 
X20~X37/X20~X37/X40~X57 
Y20~Y37/Y20~Y37/Y40~Y57 
EXT2 
48HP 
24 
24 
X40~X67/X40~X67/X60~X107 
Y40~Y67/Y40~Y67/Y60~Y107 
EXT3 
08HP 
X70~X73/X70~X73/X110~X113 
Y70~Y73/Y70~Y73/Y110~Y113 
EXT4 
08HN 
Y74~Y103/Y74~Y103/Y114~Y123 
In system application example, if the input/output of the 1
st
 MPU are less than 16, its input/output will be defined 
as 16 and thus there are no corresponding input/output for higher numbers. The input/output number of 
extension number is the sequential number from the last number of the MPU. 
 Power Input Wiring and Specification 
The power input for DVP-EH series PLC is AC input. Please pay particular attention to the following notes: 
1. Connect the AC input (100 ~ 240V) to terminals L and N. Any 110V AC or 220V AC connected to the +24V 
terminal or input points will permanently damage the PLC. 
2. The AC power inputs for the MPU and the I/O Extension Unit should be ON or OFF at the same time. 
3. Please use wires of 1.6mm or above for the grounding of the MPU. 
4. If the power-cut time is less than 10ms, the PLC still operates unaffectedly. If the power-cut time is too long or 
the power voltage drops, the PLC will stop operation and all outputs will be off. Once power is on again, the 
PLC will resume automatically. (There are latched auxiliary relays and registers inside of the PLC, please be 
aware when programming.) 
AC Input 
Type 
L
   
2.0 A
DC/DC
 
+5V
 
+24V
 
24G
 
S/S
 
X0
 
X1
 
X2
 
100~240VAC
 
 
The +24V supply output is rated at 0.5A as max. from MPU. DO NOT connect external power 
supply to this termianl. Moreover, it takes 6 ~ 7mA to drive each input point, so total of 100mA 
is needed for 16 input points. As a result, the output load of +24V should not exceed 400mA. 
Since the PLC is in control of numerous devices, operation of either one device could affect the operation of 
other devices; therefore, the breakdown of either one device would consequently be detrimental to the whole 
auto control system, and danger will thus be resulted. Please use the recommended wiring below for the power 
input: 
 
Power supply for AC loads 
 
Fuse for circuit  protection (3A  limit) 
 
Power on pilot indicator 
 
Emergency stop:  a manual stop button is provided for emergency 
to disconnect  system power. 
 
Circuit  isolation  device (System Power  Disconnect): use 
electromagnetic  contactor  and the relay to be the isolation unit of 
the power circuit to prevent the  possible instability of the system 
when the power is supplied on and off. 
 
DVP  PLC MPU (main processing unit) 
 
Class  three  grounding. 
OV
24 VDC
MC
MC
N
L
1
1
2
3
4
5
6
6
7
8
Guard
Lim it
 
 
Power supply:   
 
AC: 100 ~ 240V AC, 50/60Hz   
DC: 24V DC 
 Input/Output Point Wiring 
Input Point Wiring 
There are SINK and SOURCE types for the input signal of the input point with DC input. Definition as follows: 
Sink = Current flow into common terminal S/S 
Source = Current flows out of common terminal S/S 
S/S
X0
Sinking
 
S/S
X0
Sourcing
 
 
Input point loop equivalent circuit 
Wiring loop 
DC Type 
(DC Signal IN) 
SINK Mode 
(Current flows into the 
common terminal S/S) 
24VDC
24G
X0
S/S
+24V
SINK
+5V
 
24G
S/S X0
X1
X2
+24V
Sink Type
 
Input point loop equivalent circuit 
Wiring loop 
DC Type 
(DC Signal IN) 
SOURCE Mode 
(Current flows out of 
common terminal S/S) 
24VDC
24G
X0
S/S
+24V
SOURCE
+5V
 
24G
S/S X0
X1
X2
+24V
Source Type
 
Output Point Wiring 
 
  DO NOT wire to the No Function terminals   
•   
 
  Fuse 
 
  Diode in reverse direction  to protect the relay*1 
 
  Mutually  exclusive  outputs*2 
 
  Emergency stop:  use  an external switch 
 
  Surge  absorber*3 
 
  Conductive  loading 
 
  Incandescent  lamp  (resistive  loading) 
 
  DC supply 
Relay output wiring 
MC2
MC1
9
10
C0
C1
Y0
Y4
C2
Y2
Y3
Y5
Y1
5
2
3
7
8
1
6
7
2
5
4
MC2
MC1
 
 
  AC supply 
*1: There is no protection circuit for the Relay output in the PLC. If DC conductive loading is on, add a diode in reverse direction in 
parallel to extend the life of the Relay. The diode in reverse direction should correspond to the following specification: 
 
- The diode is able to withstand 5~10+ times loading voltage as maximum. 
 
- The forward current of the diode must be greater than loading current. 
*2: Use external hardware interlock and those in the PLC program to secure any emergent errors with safety protection. 
*3: There is no protection circuit for the Relay in  the PLC. If AC conductive loading is on, connect a surge absorber (0.1uF+ “100ohm to 
120ohm”) to reduce interference and extend the life of the Relay. 
 
  DO NOT wire to the No Function terminals   
•   
 
  Emergency  stop 
 
  Fuse 
 
  Mutually  exclusive  output*1 
 
  DC apply 
 
  Incandescent  lamp  (resistive  loading) 
 
  Diode in reverse direction  to protect the transistor*2 
 
  Conductive  loading 
Transistor output wiring 
MC2
MC1
C0
C1
Y0
Y4
C2
Y2
Y3
Y5
Y1
5
7
8
1
6
6
4
MC2
MC1
2
3
3
9
 
 
  Resistive  loading 
*1: Use external hardware interlock and those in the PLC program to secure any emergent errors with  safety  protection. 
*2: Use Zener diode (39V) inside the PLC to protect the transistor. If conductive loading is on, adding a diode in reverse direction in 
parallel is  recommended. 
 
注意事項 
  請在使用之前,詳細閱讀本使用說明書。 
  本機為開放型  (OPEN TYPE)  機殼,因此使用者使用本機時,必須將之安裝於具防塵、防潮及免於電擊/衝擊
意外之外殼配線箱內。另必須具備保護措施  (如:  特殊之工具或鑰匙才可打開)  防止非維護人員操作或意外衝
擊本體,造成危險及損壞。 
  交流輸入電源不可連接於直流類型之輸入/出信號端,否則可能造成嚴重的損壞,因此請在上電之前再次確認
電源配線。請勿在上電時觸摸任何端子。 
 
產品簡介 
 
 
謝謝您採用台達 DVP-EH 可程式控制器。EH 8 ~ 48 點擴充,含主機最大數位輸入/輸出擴充分別可達 256 點。 
 
產品外觀及各部介紹 
1
3
4
3
5
5
2
7
7
 
2
1
5
5
3
3
4
7
7
 
 
尺寸  (mm) 
機種名稱 
長 
寬 
高 
DVP08HM11N 
90 
40 
82 
DVP16HM11N 
90 
55 
82 
DVP08HN11R/T 
90 
40 
82 
DVP16HP11R/T 
90 
55 
82 
 
3
4
2
6
6
6
7
7
3
3
8
 9
1
10
11
 
 
尺寸  (mm) 
機種名稱 
長 
寬  (w) 
高 
DVP32HN00R/T 
90 
143.5 
82.2 
DVP32HP00R/T 
90 
143.5 
82.2 
DVP48HP00R/T 
90 
174 
82.2 
 
1. 
電源、低電壓指示燈 
5. 
擴充排線 
  9. 
上蓋 
2. 
輸出/入端子 
6. 
擴充機連接口上蓋 
10. 
輸入指示燈 
3. DIN
軌固定扣 
7. 
直接固定孔 
11. 
輸出燈示燈 
4. DIN
軌固定槽 
8. 
機種名稱 
 
 
機種型號 
輸入單元 
輸出單元 
機種 
電源 
點數 
形式 
點數 
形式 
DVP08HM11N 
DVP16HM11N 
16 
無 
DVP08HN11R 
DVP08HP11R 
DVP16HP11R 
繼電器 Relay 250V AC/30V DC 2A/1 點 
DVP08HN11T 
DVP08HP11T 
DVP16HP11T 
24V DC 
DC Type 
Sink/Source 
電晶體 Transistor  5  ~  30V  DC  0.3A/1 點
@40°C 
繁體中文 
輸入單元 
輸出單元 
機種 
電源 
點數 
形式 
點數 
形式 
DVP32HN00R 
32 
DVP32HP00R 
16 
16 
DVP48HP00R 
24 
24 
繼電器 Relay 250V AC/30V DC 2A/1 點 
DVP32HN00T 
32 
DVP32HP00T 
16 
16 
DVP48HP00T 
100 ~ 240V 
AC 
24 
DC Type 
Sink/Source 
24 
電晶體 Transistor  5  ~  30V  DC  0.3A/1 點
@40
°C 
 
規格 
 
電氣規格 
 
機種 
 
項目 
08HM11N 
16HM11N 
08HN11R/T  08HP11R/T  16HP11R/T  32HN00R/T  32HP00R/T  48HP00R/T 
電源電壓 
24V DC (20.4V DC ~ 28.8V DC) (-15% ~ 20%) 
100 ~ 240V AC (-15% ~ 10%), 
50/60Hz ± 5% 
消耗電力 
1W / 1.5W 
1.5W 
1.5W 
2W 
30VA 
30 VA 
30 VA 
24V DC
供應電流 
NA 
NA 
NA 
NA 
NA 
500 mA 
500 mA 
24V DC
輸出具短路保護
24V DC
輸出具短路保護 
突波電壓耐受量 
1,500V AC (Primary-secondary), 1,500V AC (Primary-PE), 500V AC (Secondary-PE) 
絕緣阻抗 
5 MΩ
以上(所有輸出/入點對地之間  500V DC) 
雜訊免疫力 
ESD: 8KV Air Discharge, EFT: Power Line: 2KV, Digital I/O: 1KV, Analog & 
Communication I/O: 250V,   
Digital I/O: 1KV, RS: 26MHz ~ 1GHz, 10V/m 
接地 
接地配線之線徑不得小於電源端 L, N 之線徑(多台 PLC 同時使用時,請務必單點接地) 
操作/儲存環境 
操作:0 ~ 55°C(溫度),  50 ~ 95%(濕度),  污染等級 2 
儲存:-25 ~ 70°C(溫度),5 ~ 95%(濕度) 
耐振動/衝擊 
國際標準規範  IEC61131-2, IEC 68-2-6 (TEST Fc)/IEC61131-2 & IEC 68-2-27 (TEST Ea) 
重量(約)(g) 
124/160 
130/120 
136/116 
225/210 
660/590 
438/398 
616/576 
認證 
 
 
 
 
 
輸入/出點規格 
輸入點電氣規格 
輸入點形式 
直流 
輸入形式 
直流(SINK 或 SOURCE) 
輸入電壓電流 
24V DC 5mA 
Off → On 16.5V DC
以上 
動作位準 
On → Off 8V DC
以下 
反應時間 
約 20ms 
電路隔離/操作指示 
光耦合器/LED On 
 
輸出點電氣規格 
輸出點形式 
繼電器-R 
電晶體-T 
電流規格 
1.5A/1
點(5A/COM) 
55°C 0.1A/1
點、50°C 0.15A/1 點、 
45°C 0.2A/1
點、40°C 0.3A/1 點(2A/COM) 
電壓規格 
250V AC,30V DC
以下 
30V DC 
75VA
(電感性) 
最大負載 
90 W
(電阻性) 
9W 
反應時間 
約 10 ms 
Off → On 15us   
On → Off 25us