Delta Electronics DTC1000 Series Prospecto

Descargar
Página de 2
Mode 
Alarm Type 
Alarm Output Operation 
Alarm output will be enabled when the temperature reaches the upper limit. 
y
 Alarm will be enabled when the PV exceeds SV + AL-H. 
ON
OFF
SV
AL-H
 
Alarm output will be enabled when the temperature reaches the lower limit. 
y
 Alarm will be enabled when the PV falls below SV – AL-L. 
ON
OFF
AL-L
SV
 
y
 Alarm will be enabled when the PV is between SV + AL-L and SV – AL-L. 
ON
OFF
AL-L
SV
AL-H
 
Alarm output will be enabled when the temperature reaches the absolute 
value of the upper and lower limits. 
y
 Alarm will be enabled when the PV exceeds AL-H or falls below AL-L. 
ON
OFF
AL-L
AL-H
 
Alarm output will be enabled when the temperature reaches the absolute 
value of the upper limit. 
y
 Alarm will be enabled when the PV exceeds AL-H. 
ON
OFF
AL-H
 
Alarm output will be enabled when the temperature reaches the absolute 
value of the lower limit. 
y
 Alarm will be enabled when the PV falls below AL-L. 
ON
OFF
AL-L
 
Standby upper/lower limit alarm 
y
 Alarm will be enabled when the PV reaches SV and exceeds SV + AL-H or 
falls below SV – AL-L. 
ON
OFF
AL-L
AL-H
SV
 
Upper limit standby alarm 
y
 Alarm will be enabled when the PV reaches SV and exceeds SV + AL-H. 
ON
OFF
SV
AL-H
 
10 
Lower limit standby alarm 
y
 Alarm will be enabled when the PV reaches SV and falls below SV – AL-L 
ON
OFF
AL-L SV
 
11 
Upper limit hysteresis alarm 
y
 Alarm will be enabled when the PV exceeds SV + AL-H and disabled when 
the PV falls below SV + AL-L. 
ON
OFF
AL-H
AL-L
 
12 
Lower limit hysteresis alarm 
y
 Alarm will be enabled when the PV falls below SV – AL-H and disabled 
when the PV exceeds SV – AL-L. 
ON
OFF
AL-H
AL-L
 
Note: AL-H and AL-L include AL1H, AL2H, AL1L and AL2L. When Output 1 is set to Alarm Output, use AL1H (1024H) and AL1L 
(1025H). When Output 2 is set to Alarm Output, use AL2H (1026H) and AL2L (1027H). 
 
 
LED Display
 
1.  When power is normal, POWER LED will be on. 
2.  After DTC1000/2000 is switched on, all LED will be on. The communication protocol will be displayed in 1 second, 
followed by the communication address in the next second. 
3.  RUN LED is on when the control is executing. 
4.  ERROR LED is on when errors occur in input, memory or communication. 
5.  When an output is executing, its corresponding output LED will be on. 
6.  AT LED flashes when PID parameters are being auto-tuned. 
7.  RX LED flashes when DTC1000/2000 receives communication signals. TX LED flashes when DTC1000/2000 
sends out communication signals. 
Communication protocol displayed on LED after the power of DTC1000/2000 is switched on: 
AT 
TX 
RX 
O1 
O2 
Err 
Run 
000: 2,400bps  001: 4,800bps   010: 9,600bps 
011: 19,200bps 100: 38,400bps   
Parity  00: None  01: Even 
       10: Odd 
0: ASCII 
1: RTU 
0:2 Stop bits 
1:1 Stop bit 
Communication address display: AT (bit 6) and Run (bit 0) are combined to binary code. 
 
 
Password Function
 
The default setting of the password is disabled. To enable the password function, enter the 4-character password in the 
specific communication address. The password is protected by 3 levels. 
1.  Level 1: Only LED status, SV and PV can be read. No settings can be modified. 
2.  Level 2: Only LED status, SV and PV can be read. Only SV can be modified. 
3.  Level 3: All SV can be read. Only SV and auto-tuning can be modified. 
4.  Level 4: No password protection. 
When a password is set (in 106EH ~ 1070H), the protection will enter Level 1. To enter other levels, enter the 
corresponding password (in 106BH ~ 106DH). After DTC1000/2000 is switched off, the protection will return to Level 1. 
To unlock the password protection, the user has to remove all the passwords (in 106EH ~ 1070H). 
The password protection level can be read in 106EH ~ 1070H: 
bit 
b0 
b1 
b2 
b3 
b4 
b5 
b6 
Status Level 
Level 2 
Level 3 
Level 1 locked 
Level 2 locked 
Level 3 locked 
Unlocked 
bit = 0 refers to no password is set. bit = 1 refers to the password has been set (b0 ~ b2). b3 ~ b6 display the current level status. 
 
 
Synchronous Communication Protocol & Auto ID Setup
 
This function allows the user to set the communication protocol of DTC2000 to the same protocol as set in the first 
DTC1000. The station IDs of DTC1000/2000 are arranged in decreasing order. Follow the steps below. 
1.  Set the auto communication ID of DTC1000 to “1” (communication address: 1022H). 
2.  Switch off DTC1000 before connecting it to DTC2000. Switch it on again. 
3.  Default communication protocol: 9,600bps, 7 bits, Even, 1 stop bit, communication address 01. 
4.  This function will consume 3 ~ 5 seconds more when you switch on your DTC.
 
 
 
RS-485 Communication
 
1.  Supports transmission speed: 2,400, 4,800, 9,600, 19,200, 38,400bps; 
2.  Does not support 7, N, 1 / 8, E, 2 / 8, O, 2 communication format; 
3.  Communication protocol: Modbus ASCII/RTU; 
4.  Function code: 03H (read Max. 8 words in register), 06H (write 1 word into register), 01H (read Max. 16 bits of 
data), 05H (write 1 bit into register). 
 
 
 
 
Address 
Setting 
Content 
Explanation 
1000H 
 
Present temperature value (PV) 
Unit: 0.1 degree. Analog input: 1EU. 
The read values below indicate the occurrence of errors: 
8002H: Temperature not acquired yet 
8003H: Temperature sensor not connected   
8004H: Incorrect sensor type 
8006H: Unable to acquire temperature, ADC input error 
8007H: Unable to read/write the memory 
1001H 
Set point (SV) 
Unit: 0.1 degree. Analog input: 1EU. 
1002H 
6,000 
Upper-limit of temperature range 
The content shall not be bigger than the range. Unit: 0.1° 
1003H 
-200 
Lower-limit of temperature range 
The content shall not be smaller than the range. Unit: 0.1° 
1004H 
12 
Input sensor type 
See the table in “Input” section. 
1005H 
Control method 
0: PID, 1: ON/OFF, 2: Manual, 3: programmable PID 
1007H 
Control cycle of Output 1 
0 ~ 99, 0: 0.5sec 
1008H 
Control cycle of Output 2 
0 ~ 99, 0: 0.5sec (Invalid when the 2 outputs are the same 
control.) 
1009H 
476 
Proportional band value 
1 ~ 9,999, Unit: 0.1°. Analog input: 1EU 
100AH 
260 
Ti value 
0 ~ 9,999 
100BH 
41 
Td value 
0 ~ 9,999 
100CH 
Default integration value 
0 ~ 1,000, Unit: 0.1% 
100DH 0 
Offset compensation value for proportional 
control (when Ti=0)) 
0 ~ 1,000, Unit: 0.1% 
100EH 
100 
COEF setting when in dual control output 
1 ~ 9,999, Unit: 0.01 
100FH 0 
Deadband setting when in dual control 
output 
-999 ~ 9,999, Unit: 0.1° or 1EU 
1010H 
Hysteresis of Output 1 
0 ~ 9,999, Unit: 0.1° or 1EU 
1011H 
Hysteresis of Output 2 
0 ~ 9,999, Unit: 0.1° or 1EU 
1012H 
Read/write output percentage of Output 1 
Unit: 0.1%. “Write” is only applicable in manual mode. 
1013H 
Read/write output percentage of Output 2 
Unit: 0.1%. “Write” is only applicable in manual mode. 
1014H 
Upper-limit regulation for analog linear output  1 scale = 2.8μA = 1.3mV 
1015H 
Lower-limit regulation for analog linear output  1 scale = 2.8μA = 1.3mV 
1016H 
Temperature offset regulation value   
-999 ~ +999, Unit: 0.1° or 1EU 
1020H 
Output mode for Alarm 1 
See “Alarm Output” section. 
1021H 
Output mode for Alarm 2 
See “Alarm Output” section. 
1022H 
Communication flag auto-set 
0: Communication banned, 1: Communication auto-set 
1024H 
40 
Upper limit for Alarm 1 
See “Alarm Output” section. 
1025H 
40 
Lower limit for Alarm 1 
See “Alarm Output” section. 
1026H 
40 
Upper limit for Alarm 2 
See “Alarm Output” section. 
1027H 
40 
Lower limit for Alarm 2 
See “Alarm Output” section. 
102AH 
 
Read/write status 
b1: ALM2, b2:
 
°C, b3:
 
°F, b4: ALM1, b5: O2, b6:O1, b7: AT 
102CH 
Positive/negative proportional output 
0: positive, 1: negative 
102EH 
 
LED status 
b0: RUN, b1: ERR, b2: O2, b3: O1, b4: RX, b5:TX b6: AT 
102FH 
 
Software version 
V1.00 is indicated as 0x100 
1030H 
No. of start pattern 
0 ~ 7 
1032H 
 
Remaining time of the executed step 
Unit: second 
1033H 
 
Remaining time of the executed step 
Unit: minute 
1034H 
 
No. of currently executed step 
0 ~ 7 
1035H 
 
No. of currently executed pattern 
0 ~ 7 
1037H 
1,000 
Upper limit of proportional output 
0 ~ 100% upper limit of analog output, Unit: 0.1% 
1038H 
Lower limit of proportional output 
0 ~ 100% lower limit of analog output, Unit: 0.1% 
1040H~ 
1043H 
Number of steps in a pattern 
0 ~ 7 = N refers to the pattern will be executed from Step 0 
to Step N. 
1050H~ 
1053H 
Additional number of cycles for a pattern 
0 ~ 199 refers to the pattern will be executed for 1 ~ 200 
times. 
1060H~ 
1063H 
No. of the link pattern for the current 
pattern 
0 ~ 8, 8 refers to end of the program. 0 ~ 7 refers to the 
next pattern No. following the current pattern. 
1068H 
Run/Stop setting 
0: Stop, 1: Run, 2: Program end, 3: Program hold 
1069H 
Control selection of Output 1 
0: Heating, 1: Cooling, 2: Alarm, 3: Proportional output 
106AH 
Control selection of Output 2 
0: Heating, 1: Cooling, 2: Alarm 
106BH 0 
Unlock Level 1 password protection. 
Read/write allowed 
Shall be the same as Level 1 password (106E) 
106CH 0 
Unlock Level 2 password protection. Use 
Level 3. 
Shall be the same as Level 2 password (106F) 
106DH 0 
Unlock Level 3 password protection. Use 
Level 2 
Shall be the same as Level 3 password (1070) 
106EH 0 
Unlock Level 1 password protection/Set up 
password 
Unlock password before setting it up. 
106FH 0 
Unlock Level 2 password protection/Set up 
password 
Unlock password before setting it up. 
1070H 0 
Unlock Level 3 password protection/Set up 
password 
Unlock password before setting it up. 
1071H 
Read/write communication address 
1 ~ 247 
1072H 
Read/write communication format 
1: RTU, 0: ASCII 
1073H 2 
Read/write 
communication speed 
0 ~ 4: 2,400 ~ 38,400 
1074H 
Read/write communication data length 
0: 8 bits, 1: 7 bits 
1075H 
Read/write parity bit 
0: None, 1: Even, 2: Odd   
1076H 
Read/write stop bit 
0: 2 stop bits, 1: 1 stop bit 
2000H~ 
203FH 
SV temperature for Pattern 0 ~ 7. 
SV for Pattern 0 is set in 2000H ~ 2007H 
Unit: 0.1° 
2080H~ 
20BFH 
Execution time for Pattern 0~7.   
Time for Pattern 0 is set in 2080H ~ 2087H 
0 ~ 900 (1 scale = 1 minute) 
5.  Address and content of the bit register (read bits are stored starting from LSB, and written data is FF00H, set the 
bit as 1. 0000H sets the bits data to “0”). 
0811H 
Temperature unit display 
0:°F, 1: °C (Default) 
0813H 
Read/write auto-tuning status 
0: End (Default), 1: Start 
0814H 
Run/Stop setting 
0: Stop, 1: Run (Default) 
0815H 
Program hold flag 
1: Program hold 
0816H 
Program stop flag 
1: Program stop 
6.  Communication format: Command 01: read bit, 05: write bit, 03: read word, 06: write word.
 
 
 
y
 ASCII Mode 
Read Command 
Read Response Message 
Write Command 
Write Response Message 
Start word 
’:’  ’:’ 
Start word 
’:’  ’:’ 
Start word 
’:’ 
’:’ 
Start word 
’:’  ’:’ 
Machine address 1 
‘0’  ‘0’ 
Machine address 1 
‘0’  ‘0’ 
Machine address 1 
‘0’  ‘0’ 
Machine address 1 
‘0’  ‘0’ 
Machine address 0 
‘1’  ‘1’ 
Machine address 0 
‘1’  ‘1’ 
Machine address 0 
‘1’  ‘1’ 
Machine address 0 
‘1’  ‘1’ 
Command 1 
‘0’  ‘0’ 
Command 1 
‘0’  ‘0’ 
Command 1 
‘0’  ‘0’ 
Command 1 
‘0’  ‘0’ 
Command 0 
‘3’  ‘1’ 
Command 0 
‘3’  ‘1’ 
Command 0 
‘6’  ‘5’ 
Command 0 
‘6’  ‘5’ 
‘1’  ‘0’ 
‘0’  ‘0’ 
‘1’  ‘0’ 
‘1’  ‘0’ 
‘0’  ‘8’ 
Length of response data 
(byte) 
‘4’  ‘2’ 
‘0’  ‘8’ 
‘0’  ‘8’ 
‘0’  ‘1’ 
‘0’  ‘1’ 
‘0’  ‘1’ 
‘0’  ‘1’ 
Read staring address of 
data/bit 
‘0’  ‘0’ 
‘1’  ‘7’ 
Write data address 
‘1’  ‘0’ 
Write data address 
‘1’  ‘0’ 
‘0’  ‘0’ 
‘F’  ‘0’ 
‘0’  ‘F’ 
‘0’  ‘F’ 
‘0’  ‘0’ 
Data content in 
1000H/081xH 
‘4’  ‘1’ 
‘3’  ‘F’ 
‘3’  ‘F’ 
‘0’  ‘0’ 
‘0’ 
 
‘E’  ‘0’ 
‘E’  ‘0’ 
Read length of data/bit 
(word/bit) 
‘2’  ‘9’ 
‘0’ 
 
To write data content 
‘8’  ‘0’ 
Write data content 
‘8’  ‘0’ 
LRC1 check   
‘E’  ‘D’ 
‘0’ 
 
LRC1  
‘F’  ‘E’ 
LRC1  
‘F’  ‘E’ 
LRC0 check 
‘A’  ‘D’ 
Data content in 1001H 
‘0’ 
 
LRC0  
‘D’  ‘3’ 
LRC0  
‘D’  ‘3’ 
End word 1 
CR  CR 
LRC1 check   
‘0’  ‘E’ 
End word 1 
CR  CR 
End word 1 
CR  CR 
End word 0 
LF  LF 
LRC0 check 
‘3’  ‘4’ 
End word 0 
LF  LF 
End word 0 
LF  LF 
 
 
 
End word 1 
CR  CR 
 
 
 
 
 
 
 
 
 
End word 0 
LF  LF 
 
 
 
 
 
 
y
 LRC Check 
LRC check sums up from “machine address” to “data content”, e.g. 01H + 03H + 10H+ 00H + 00H + 02H = 16H. Obtain 2’s 
complement EA. 
y
 RTU Mode 
Read Command 
Read Response Message 
Write Command 
Write Response Message 
Machine address 
01H  01H 
Machine address 
01H  01H 
Machine address 
01H  01H 
Machine address 
01H  01H 
Command 03H  01H 
Command 03H  01H 
Command 06H  05H 
Command 06H  05H 
10H  08H 
10H  08H 
10H  08H 
Read start address 
of data 
00H  10H 
Length of response 
data (byte) 
04H  02H 
Write data address 
01H  10H 
Write data address 
01H  10H 
00H  00H 
01H  17H 
03H  FFH 
03H  FFH 
Read length of data 
(bit/word) 
02H  09H 
Data content 1 
F4H  01H 
Write data content 
20H  00H 
Write data content 
20H  00H 
CRC low byte 
C0H  BBH 
03H 
 
CRC low byte 
DDH  8FH 
CRC low byte 
DDH  8FH 
CRC high byte 
CBH  A9H 
Data content 2 
20H 
 
CRC high byte 
E2H  9FH 
CRC high byte 
E2H  9FH 
 
 
 
CRC low byte 
BBH  77H   
 
 
 
 
 
 
 
 
CRC high byte 
15H  88H   
 
 
 
 
 
y
 CRC Program Example
 
unsigned int reg_crc = 0xffff; i = 0;   
while (length--) 
{  
  reg_crc ^= RTUData[i];   
 i ++;  
  for (j = 0; j < 8; j++) 
 {  
 
if (reg_crc & 0x01) 
reg_crc = (reg_crc >> 1) ^ 0xA001;   
 
else   
reg_crc = reg_crc >> 1;   
 } 
}  
return(reg_crc); 
 
 
Installation
 
How to connect maximum 8 DTC1000/2000 controllers by using DIN rail. 
 
 
 
 
 
How to Set Up Current Input 
For general input 
For current input (4 ~ 20mA, 0 ~ 20mA) 
JU MPER
PIN HEADER
JP1
DEFAU LT SETTING
 
J UMPER
PIN HEADER
JP1
 
 
The content of this instruction sheet may be revised without prior notice. Please consult our distributors or 
download the most updated version at http://www.delta.com.tw/industrialautomation