Delta Electronics RTU-485 Prospecto

Descargar
Página de 2
 
5011668000-RU00
2007-08-13
 
 
Warning
 
 Please read this instruction sheet carefully before use. 
 Switch off the power before wiring. 
 RTU-485 is an OPEN-TYPE device and therefore should be installed in an enclosure free of airborne dust, 
humidity, electric shock and vibration. The enclosure should prevent non-maintenance staff from operating the 
device (e.g. key or specific tools are required to open the enclosure) in case danger and damages on the 
device may occur.
 
 DO NOT touch the internal circult in one minute after the power is switched off. 
 DO NOT connect input AC power supply to any of the I/O terminals; otherwise serious damage may occur. 
Check all the wiring again before switching on the power and DO NOT touch any terminal when the power is 
switched on. Make sure the ground terminal 
  is correctly grounded in order to prevent electromagnetic 
interference. 
 
 Introduction 
Thank you for choosing Delta RTU-485 communication module. RTU-485 is a Modbus remote I/O 
communication module for Delta's PLC to remote-control Slim series DI/DO and AI/AO extension units. 
As a standard Modbus slave, RTU-485 is compatible with other master station complying with Modbus 
protocol. 
 
Product Profile & Outline 
S
G
D
-
D
+
ST O P
R UN
R
T
U
-4
8
5
R UN
A LA RM
PO W ER
R S- 4 85
1
2
3
5
6
9
8
7
4
10
11
12
13
14
15
16
 
Unit: mm 
1. POWER indicator 
9. Mounting hole for extension unit 
2. RUN indicator 
10. Nameplate 
3. ALARM indicator 
11. Extension port for extension unit 
4. RUN/STOP switch 
12. DIN rail slot (35mm) 
5. Communication indicator 
13. Fastening hole for extension unit 
6. Address setup DIP switch 
14. DIN rail clip 
7. Communication mode setup DIP switch 
15. Mounting rail for extension unit 
8. RS-485 communication port 
16. Power input 
 
 
 
 
ENGLISH 
 Specifications 
 RTU-485 Connector 
Type 
Removable  3-pin  connector 
Transmission 
method 
RS-485 
Transmission  cable 
2 twisted  isolation  cables 
Electrical  isolation 
500V DC 
 Communication 
Valid  communication 
address 
1 ~ F0 (decimal: 1 ~ 240) 
Series  transmission 
speed 
1,200/2,400/4,800/9,600/19,200/38,400/57,600/115,200 bps (bits  per  second) 
Communication 
mode 
7,E,1-ASCII / 7,O,1-ASCII / 7,E,2-ASCII / 7,O,2-ASCII / 7,N,2-ASCII / 8,E,1-ASCII / 
8,O,1-ASCII / 8,N,1-ASCII / 8,N,2-ASCII / 8,E,1-RTU / 8,O,1-RTU / 8,N,1-RTU/ 
8,N,2-RTU 
 Electrical Specification 
Power voltage 
24V DC (-15% ~ 20%) (with DC  input polarity reverse  protection)   
 Environment 
Noise  immunity 
ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge, 4KV  Contact  Discharge 
EFT (IEC 61131-2, IEC 61000-4-4): Power Li4ne: 2KV, Digital I/O: 1KV 
Analog & Communication I/O: 1KV 
Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV 
RS (IEC 61131-2, IEC 61000-4-3): 80MHz ~ 1000MHz , 1.4GHz ~ 2.0GHz , 10V/m 
Operation/storage 
Operation: 0ºC ~ 55ºC (temperature), 50 ~ 95% (humidity),  pollution  degree 2 
Storage: -25ºC ~ 70ºC (temperature), 5 ~ 95% (humidity) 
Shock/vibration 
immunity 
International  standards: IEC61131-2
、IEC 68-2-6 (TEST Fc)/IEC61131-2 & IEC 68-2-27 
(TEST Ea) 
Standards 
IEC 61131-2, UL508 
 Components 
 RUN/STOP Switch 
Status 
Explanation 
1. RUN indicator on RTU-485 is On. 
   
2. AI/AO extension  unit  in RUN status. 
1. AI/AO extension  unit  switches  from RUN to STOP status. 
RUN  STOP 
2. Y points on DI/DO extension  unit are  all Off. 
1. RUN indicator on RTU-485 is Off. 
2. AI/AO extension  unit  in  STOP  status. 
3. Communication control  is  not allowed in AI/AO extension  unit. 
STOP 
4. Communication control  is  not allowed in DI/DO extension  unit. 
1. RTU-485 re-detects the number of points in DI/DO unit and the 
number of  AI/AO units. 
 
ST OP
RUN
 
STOP  RUN 
2. AI/AO extension unit switches from STOP to RUN status. 
 
 Address Setup DIP Switch
 
DIP Switch  Setting 
Explanation 
H’01 ~ H’F0 
For valid RTU-485 address, the definition of ID0 ~ ID7 
are: 2
0
, 2
1
, 2
, … 2
, 2
H’00, H’F1 ~ H’FF 
In the Modbus protocol, H’00 is defined as broadcast 
mode. H’F1 ~ H’FF are  incorrect RTU-485  addresses. 
 
 
 Communication Mode Setup DIP Switch 
The communication setup switch is a set of 8-bit DIP switches. PA0 ~ PA3 are for setting up RTU-485 
communication mode, DR0 ~ DR2 are for setting up the series transmission speed, and A/R is for setting 
up ASCII/RTU mode. There are 13 communication modes and 8 series transmission speeds available. 
PA3 
PA2 
PA1 
PA0 
A/R 
Communication  mode 
OFF 
OFF 
OFF 
OFF 
ON 
7,E,1-ASCII 
OFF 
OFF 
OFF 
ON 
ON 
7,O,1-ASCII 
OFF 
OFF 
ON 
OFF 
ON 
7,E,2-ASCII 
OFF 
OFF 
ON 
ON 
ON 
7,O,2-ASCII 
OFF 
ON 
OFF 
OFF 
ON 
7,N,2-ASCII 
OFF 
ON 
OFF 
ON 
ON 
8,E,1-ASCII 
OFF 
ON 
ON 
OFF 
ON 
8,O,1-ASCII 
OFF 
ON 
ON 
ON 
ON 
8,N,1-ASCII 
ON 
OFF 
OFF 
OFF 
ON 
8,N,2-ASCII 
OFF 
ON 
OFF 
ON 
OFF 
8,E,1-RTU 
OFF 
ON 
ON 
OFF 
OFF 
8,O,1-RTU 
OFF 
ON 
ON 
ON 
OFF 
8,N,1-RTU 
ON 
OFF 
OFF 
OFF 
OFF 
8,N,2-RTU 
Other settings  of PA3, PA2, PA1, PA0 and A/R will be regarded as invalid 
communication modes 
 
 
DR2 
DR1 
DR0 
Series Transmission  speed 
OFF 
OFF 
OFF 
1,200 bit/s 
OFF 
OFF 
ON 
2,400 bit/s 
OFF 
ON 
OFF 
4,800 bit/s 
OFF 
ON 
ON 
9,600 bit/s 
ON 
OFF 
OFF 
19,200 bit/s 
ON 
OFF 
ON 
38,400 bit/s 
ON 
ON 
OFF 
57,600 bit/s 
ON 
ON 
ON 
115,200  bit/s 
 Function Codes Supported by RTU-485 
RTU-485 complies with the standard Modbus protocol, supporting the 7 function codes, H’01, H’02, H’03, 
H’05, H’06, H’0F, and H’10. Please refer to the standard Modbus protocol for the specific data format of 
each function code. 
Function  code 
Function 
Data type 
Applicable  address 
H’01 
Read the output status of bit 
device 
bit 
DO area: H’0500 ~ H’057F 
H’02 
Read the input status of bit 
device. 
bit 
DI area: H’0400 ~ H’047F 
Special function  area: H’0000 ~ H’001F 
CR of the 1
st
 AI/AO unit: H’1600 ~ H’1630 
CR of the 2
nd
 AI/AO unit: H’1640 ~ H’1670 
CR of the 3
rd
 AI/AO unit: H’1680 ~ H’16B0 
CR of the 4
th 
AI/AO unit: H’16C0 ~ H’16F0 
CR of the 5
th
 AI/AO unit: H’1700 ~ H’1730 
CR of the 6
th
 AI/AO unit: H’1740 ~ H’1770 
CR of the 7
th
 AI/AO unit: H’1780 ~ H’17B0 
H’03 
Read  register 
word 
CR of the 8
th
 AI/AO unit: H’17C0 ~ H’17F0 
H’05 
Write single datum into  bit 
device 
bit 
DO area: H’0500 ~ H’057F 
RUN/STOP RTU module: H’0003 
H’06 
Write  single datum  into  register 
word 
Applicable to CR with write attribute in the 1
st
 
~ 8
th
 AI/AO  extension  unit. 
H’0F 
Write many data into bit device 
bit 
DO area: H’0500 ~ H’057F 
RUN/STOP RTU module: H’0003 
H’10 
Write many data into register 
word 
Applicable to CR with write attribute in the 1
st
 
~ 8
th
 AI/AO  extension  unit. 
Example: Use function code 03 to read CR0 and CR1 in the 1
st
 AI/AO extension unit: (ASCII mode) 
The request message sent from master PLC to RTU-485 is “: 01 03 16 00 00 02 E4 CR LF” 
The responding message sent from RTU-485 to the master PLC is “: 01 03 04 00 88 00 00 70 CR LF” 
Note: 
1. RTU-485 can only read and write one AI/AO extension unit at the same time.   
2. RTU-485 is able to read/write maximum 16 words at a time in the communication control.   
 
 
 
 
 LED Indicators 
 POWER Indicator 
LED status 
Indication 
How to deal with it 
Off 
No power 
Check if the power and connection of 
RTU-485 work normally. If both  work 
normally, your RTU-485  malfunctions. 
Please change to a new RTU-485. 
Constantly On  in green 
RTU-485 module  is  powered 
 RUN Indicator
 
LED status 
Indication 
How to deal with it 
Off 
RTU-485 and the connected AI/AO 
extension unit  are  in  STOP status.   
- 
Constantly On  in green 
RTU-485 and the connected AI/AO 
extension  unit  are  in RUN status. 
 ALARM Indicator 
LED status 
Indication 
How to deal with it 
Red  light flashes 
Low power voltage 
Adjust the voltage supplied to RTU-485 to 
normal  voltage. 
Incorrect  communication  format 
Reset to the communication format 
supported  by RTU-485 and re-power the 
module after  the setup. 
Incorrect  station  No. 
Check if the station No. is within H’01 ~ 
H’F0. 
Constantly On  in red 
1. No  extension  unit  connected 
2. More than 8 extension  unit 
connected 
3. More then 128 I/O points in the 
extension  unit. 
1. Make sure  the extension unit  is correctly 
connected. 
2. Make sure the number of connected 
extension units is  less than  8. 
3. Make sure the number of I/O points is 
less  than128. 
 RS-485 Indicator 
LED status 
Indication 
How to deal with it 
Red  light  flashes  during 
communication 
The LED will flash once when RTU-485 
and the master completes  the 
communication  of 1  message. 
- 
 
 
 
注意事項
 
  請在使用之前,詳細閱讀本使用說明書。 
 
實施配線,務必關閉電源。 
 
本機為開放型(OPEN TYPE)機殼,因此使用者使用本機時,必須安裝於具防塵、防潮及免於電擊
/衝擊意外的外殼配線箱內。另必須具備保護措施(如:特殊的工具或鑰匙才可打開),防止非維護
人員操作或意外衝擊本體,造成危險及損壞。 
 
輸入電源切斷後,一分鐘之內,請勿觸摸內部電路。 
 
交流輸入電源不可連接於輸入/輸出信號端,否則可能造成嚴重損壞。請在上電前再次確認電源配線,
且請勿在上電時觸摸任何端子。本體上的接地端子 務必正確的接地,以提高產品抗雜訊能力。 
 
產品簡介 
感謝您使用台達 RTU-485 通訊模組,RTU-485 為 Modbus 遠端 I/O 通訊模組,可實現台達可程式控制器對
Slim
系列 DI/DO,AI/AO 擴充模組的遠端控制  。此外,RTU-485 做為標準的 Modbus 從站設備,也可以相
容其他遵循 Modbus 協定的主控設備。 
 
產品外觀及各部介紹
產品外觀及各部介紹
產品外觀及各部介紹
產品外觀及各部介紹 
S
G
D
-
D
+
ST O P
R UN
R
T
U
-4
8
5
R UN
A LA RM
PO W ER
R S- 4 85
1
2
3
5
6
9
8
7
4
10
11
12
13
14
15
16
 
尺寸單位:mm 
1. POWER
指示燈 
9. 
擴充機定位孔 
2. RUN
指示燈 
10. 
銘牌說明 
3. ALARM
指示燈 
11. 
擴充機連介面 
4. RUN/STOP
開關 
12. DIN
軌槽  (35mm) 
5. Communication
指示燈 
13. 
擴充機固定扣 
6. 
站號設置開關 
14. DIN
固定扣 
7. 
通訊模式設置開關 
15. 
擴充機固定槽 
8. RS-485
通訊口 
16. 
電源輸入口 
 
繁體中文
繁體中文
繁體中文
繁體中文    
 
功能規格 
 RTU-485 
連接器
連接器
連接器
連接器 
接頭 
可插拔式 3Pin 連接器 
傳輸方式 
RS-485 
傳輸電纜 
2
絞線式隔離線 
電氣隔離 
500V DC 
 
通訊
通訊
通訊
通訊
 
有效通訊位址  1 ~ F0(十進位為 1 ~ 240) 
串列傳輸速率  支援 1,200、2,400、4,800、9,600、19,200、38,400、57,600、115,200 bps(位元/秒) 
通訊模式 
支援 7,E,1-ASCII、7,O,1-ASCII、7,E,2-ASCII、7,O,2-ASCII、7,N,2-ASCII、8,E,1-ASCII、8,O,1-ASCII、
8,N,1-ASCII
、8,N,2-ASCII、8,E,1-RTU、8,O,1-RTU、8,N,1-RTU、8,N,2-RTU 
 
電氣規格
電氣規格
電氣規格
電氣規格 
電源電壓 
24V DC (-15% ~ 20%)
(具直流輸入電源極性反接保護) 
 
環境規格
環境規格
環境規格
環境規格 
雜訊免疫力 
ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge
,4KV Contact Discharge 
EFT (IEC 61131-2, IEC 61000-4-4): Power Line: 2KV, Digital I/O: 1KV 
Analog & Communication I/O: 1KV 
Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV 
RS (IEC 61131-2, IEC 61000-4-3): 80MHz~1000MHz ,  1.4GHz~2.0GHz , 10V/m 
操作/儲存環境 
操作:0ºC ~ 55ºC(溫度)、50 ~ 95%(濕度)、污染等級  2 
儲存:-25ºC ~ 70ºC(溫度)、5 ~ 95%(濕度) 
耐震動/衝擊 
國際標準規範  IEC61131-2、IEC 68-2-6 (TEST Fc)/IEC61131-2 & IEC 68-2-27 (TEST Ea) 
標準 
IEC 61131-2
、UL508  標準 
 
各部元件介紹 
 RUN/STOP
開關
開關
開關
開關 
狀  態 
說  明 
1. RTU-485
模組的RUN燈亮 
RUN 
2. AI/AO
擴充模組處於RUN狀態 
1. AI/AO
擴充模組由RUN切換到STOP狀態 
RUN  STOP 
2. DI/DO
的Y點全部變為OFF狀態 
1. RTU-485
模組的RUN燈熄滅 
2. AI/AO
擴充模組處於STOP狀態 
3. AI/AO
擴充模組不可通訊控制 
STOP 
4. DI/DO
擴充機不可通訊控制 
1. RTU-485
模組重新偵測擴充機DI/DO點數和AI/AO台數 
S TOP
R U N
 
STOP  RUN 
2. AI/AO