Delta Electronics DTV Prospecto

Descargar
Página de 2
Mode 
Alarm Type 
Alarm Output Operation 
Standby upper/lower limit alarm: Alarm will be enabled when the PV reaches SV and 
exceeds SV + AL-H or falls below SV – AL-L.   
ON
OFF
AL-L
AL-H
SV
 
Upper limit standby alarm: Alarm will be enabled when the PV reaches SV and exceeds 
SV + AL-H. 
ON
OFF
SV
AL-H
 
10 
Lower limit standby alarm: Alarm will be enabled when the PV reaches SV and falls below 
SV – AL-L. 
ON
OFF
AL-L
SV
 
11 
Upper limit hysteresis alarm: Alarm will be enabled when the PV exceeds SV + AL-H. 
Alarm will be disabled when the PV falls below SV + AL-L. 
ON
OFF
AL-L
AL-H
 
12 
Lower limit hysteresis alarm: Alarm will be enabled when the PV falls below SV – AL-H. 
Alarm will be disabled when the PV exceeds SV – AL-L. 
ON
OFF
AL-L
AL-H
 
14 
Programmable STOP: Alarm will be enabled when the program is in STOP status. 
 
15 
Programmable RAMP UP: Alarm will be enabled when the program is in RAMP UP 
status. 
 
16 
Programmable RAMP DOWN: Alarm will be enabled when the program is in RAMP 
DOWN status. 
 
17 
Programmable SOAK: Alarm will be enabled when the program is in SOAK status. 
 
18 
Programmable RUN: Alarm will be enabled when the program is in RUN status.   
 
Note: AL-H and AL-L include AL1H, AL2H and AL1L, AL2L. There is no mode 13 (reserved for CT function). 
 
 
PID Programmable Control
 
Functions and Parameter Setting: 
The PID programmable control includes 8 patterns (Pattern 0 ~ 7). Each pattern contains 8 steps (Step 0 ~ 7) and 
parameters: link pattern, cycle and the number of steps. 
Start Pattern 
This parameter can be set in the operation mode. The user can set up which pattern is the start 
pattern for the programmable control. This function is only available when the program is in STOP status.   
Step: Includes the settings of the two parameters, set point X and execution time T, indicating that the set point (SV) 
has to rise to temperature X after the period of execution time T. If the result of the set point X is the same as that of 
the previous setting, the process is called Soak; otherwise, it is called Ramp. Therefore, the programmable control is 
also known as Ramp/Soak control.   
The default setting of the first step program is Soak control. The temperature will first rise to the set point X and 
remain at X. The total execution time is T.   
Link Pattern: For example, if the parameter 
  is set as 2, it refers to the execution of pattern 2 will follow the 
execution of pattern 0. If the link pattern is set as 
, it refers to the program will end after the execution of the 
pattern is completed and the temperature will remain at the SV for the last step.   
Cycle: The additional number of cycles for a pattern. For example, if the parameter 
  is set as 2, it refers to 
pattern 4 has to execute twice additionally, totaling the executions to 3 times including the original one.   
The Number of Steps: The number of steps in each pattern (range: 0 ~ 7). For example, if the parameter 
 is 
set as 2, it refers to pattern 7 will execute step 0 ~ step 2 and other steps will not be executed.   
The Execution: 
1.  When the parameter 
  is set as 
, the program will start its execution from step 0 of the start pattern. 
2.  When the parameter 
  is set as 
, the program will stop and the control output will be disabled. 
3.  When the parameter 
  is set as 
, the program will stop and the temperature will stop at the SV before 
the program stops. When you select 
  again, the program will execute again from step 0 of the start pattern. 
4. When the parameter 
  is set as 
, the program will stop and the temperature will stop at the SV before 
the program stops. When you select 
  again, the program will resume the step before the program stops 
and execute by the remaining time. 
Display: 
In PID programmable control, some SVs are re-set as P-XX. P refers to the current pattern and XX refers to the 
current step. Press 
 
  to modify the display. 
Select 
  and press 
. SV will display the target temperature for the current step. 
Select 
  and press 
. SV will display the remaining time of the current step. 
 
 
PID Control
 
In PID control, you can select any one of the 4 groups of PID parameter (P, I, D, IOF). After auto-tuning, the PID value 
and the temperature SV will be stored into the selected PID parameter. 
 ~ 
PIDn, n = 0 ~ 4. 0 ~ 3 are the corresponding selected PID parameter.   
 refers to 
auto-selected PID and the program will automatically select a most useful PID parameter based on the current SV. SV 
displays will be 
 ~ 
  corresponding to n = 0 ~ 3. 
 ~ 
The SV for the selected PID parameter, can be set by the user or auto-generated by auto-tuning.
 
 
 
Valve Control
 
Heaters and coolers can be used to control the temperature and the openness of the valve in order to control the flow 
of the medium. Current and voltage can control the openness of the valve; however, the most direct and economic 
way to control the openness of the valve is the relay. To control the valve by voltage and current, you can use the DTB 
series analog output controller. If you tend to use relay for the control output, you have to choose the valve function in 
DTV series. The two control outputs are relay output for the forward/reverse running of the motor to drive the opening 
and closing of the valve. Control output1 controls the opening of the valve and control output 2 controls the closing of 
the valve in order to adjust the position of the valve. In order to detect the position of the valve, DTV is able to receive 
“feedback signal” and “no feedback signal”. When there is no feedback signal and the valve is fully open, control 
output 1 will output continuously. If at the moment the valve is fully closed, control output 2 will output continuously. If 
the valve you use is with feedback output, you can connect the output of the valve to the feedback part of DTV and set 
  to On to precisely control the openness of the valve. If there is no feedback signal or the feedback signal is 
incorrect, and the pre-set openness of the valve is not reached after twice as long as the time set in the parameter 
, the program will automatically switch back to the no feedback state. To ensure the correctness of the valve 
control, please make sure that you have set up the parameters below: 
 
: Time required from the valve fully closed to fully open. This parameter has to be correct when the valve is 
without feedback signal; otherwise, the accuracy for the temperature control will be affected. The PID control will 
correspond to the openness of the valve according to the setting of this parameter. 
DeadBand value of the valve. The parameter is to prevent frequent movement of the valve. For example, 
assume the DeadBand is 4%, PID control will correspond to the openness of the valve within 4% and the valve will 
not move within the range unless the value is accumulated and exceeds 4%. If the Deadband value is too small and 
the valve is set to have feedback signals, moving back and forth of the valve will shorten the life of the valve motor. 
With or without feedback signals. 
When 
  is set as “On”, it refers to “with feedback signals” and the following parameters will be displayed.   
a) 
: Automatically adjusting the upper/lower limit of the valve feedback. This parameter will only be displayed 
when 
  is set as 
. When this parameter is set as On, the relay will enable the forward and reverse 
running of the motor in order to calculate the time needed from the valve fully closed to fully open and the 
feedback signal of fully closed and open. The feedback signal is the hardware D/A value of the valve control, 
which is for the calculation of the valve controller. 
b) 
: Upper limit of the valve signal. Set 
  as “On”, can be set automatically or manually. 
c) 
Lower limit of the valve signal. Set 
  as ”On”, can be set automatically or manually.
 
 
 
Auto/Manual Mode Switch
 
A/M indicator On refers to manual mode; A/M indicator Off refers to auto mode. Besides On/Off, PID, programmable 
and manual controls, the valve control is also able to forcibly switch to manual control (fixing the openness of the 
valve, unit: % from valve fully closed to fully open) when in PID control mode. You simply need to press 
 
in PID 
control mode to switch to manual mode and A/M indicator will be On. Press 
  again to return to PID control and A/M 
indicator will be Off.   
 
 
Upper/Lower Limits of Valve Openness
 
Assume we would like the maximum openness of the valve to be 80% and the minimum to be 20%, set the parameter 
  as 80 and 
  as 20, and the valve openness of PID control, programmable control and manual control 
will fall within this range.
 
 
 
RS-485 Communication
 
1.  Supports transmission speed 2,400bps, 4,800bps, 9,600bps, 19,200bps and 38,400bps; does not support 
communication format 7, N, 1/8, E, 2/8, O, 2. Communication protocol: Modbus (ASCII or RTU). Function: 03H 
(able to read max. 8 words in the register), 06H (able to write 1 word into the register), 01H (able to read max. 16 
bits of data), 05H (able to write 1 bit into the register). 
2.  Address and content of the data register. 
Address 
Content 
Explanation 
1000H 
Present temperature value (PV) 
Unit: 0.1 degree, updated every 0.4 second. 
The read values below indicate the occurrence of errors: 
8002H: temperature not acquired yet 
8003H: temperature sensor not connected 
8004H: wrong sensor type 
8006H: unable to acquire temperature, ADC input error 
8007H: unable to read/write the memory 
1001H 
Set point (SV) 
Unit: 0.1 degree 
1002H 
Upper limit of temperature range 
The content shall not be bigger than the range. 
1003H 
Lower limit of temperature range 
The content shall not be smaller than the range. 
1004H 
Input sensor type 
See “Types of Temperature Sensors and Temperature Range" table. 
1005H 
Control method 
0: PID; 1: On/Off; 2: manual control; 3: PID programmable control 
1006H 
Selecting heating/cooling control 
0: heating; 1: cooling 
1009H 
Proportion band value 
0.1 ~ 999.9 
100AH 
Ti value 
0 ~ 9,999 
100BH 
Td value 
0 ~ 9,999 
100CH 
Default integration value 
0 ~ 100%, unit: 0.1% 
100DH 
Offset compensation value for 
proportional control (when Ti = 0) 
0 ~ 100%, unit: 0.1% 
1010H 
SV of output hysteresis 
0 ~ 9,999 
1012H 
Read/write of output percentage 
Unit: 0.1%, only applicable in manual control mode 
1014H 
Upper limit regulation for analog linear 
output 
1 scale = 2.8μA = 1.3mV 
1015H 
Lower limit regulation for analog linear 
output 
  1 scale = 2.8μA = 1.3mV 
1016H 
Temperature offset regulation value 
-99.9 ~ +99.9, unit: 0.1 
1017H 
Analog decimal point setting 
0 ~ 3 
1018H 
Time from valve fully closed to fully open 
0.1 ~ 999.9 
1019H 
DeadBand setting of valve 
0 ~ 100%, unit: 0.1% 
101AH 
Upper limit for valve feedback signal 
0 ~ 1,024 
101BH 
Lower limit for valve feedback signal 
0 ~ 1,024 
101CH 
PID group setting 
0 ~ 4 
101DH 
SV for the corresponding PID setting 
In valid range. Unit: 0.1 
101EH 
Upper limit for control output 
Lower limit for control output ~ 100%, unit: 0.1% 
101FH 
Lower limit for control output 
0 ~ Upper limit for control output, unit: 0.1% 
1020H 
Output mode for alarm 1 
See “Alarm Output” section. 
1021H 
Output mode for alarm 2 
See “Alarm Output” section. 
1023H 
System alarm setting 
0: None (default); 1 ~ 2: Set alarm 1 ~ alarm 2 
1024H 
Upper limit for alarm 1 
See “Alarm Output” section. 
1025H 
Lower limit for alarm 1 
See “Alarm Output” section. 
1026H 
Upper limit for alarm 2 
See “Alarm Output” section. 
1027H 
Lower limit for alarm 2 
See “Alarm Output” section. 
102AH 
Read/write LED status 
b0: °F; b1: °C; b2: ALM2; b3: x; b4: OUT1; b5: OUT2; b6: AT; b7: ALM1 
102BH 
Read/write key status 
b0: Set; b1: Select; b2: Up; b3: Down; 0 refers to push. 
102CH 
Panel lock status 
0: normal; 1: lock all; 11: SV adjustable; 111: SV adjustable, A/M 
available 
102FH 
Software version 
V1.00 refers to 0x100 
1030H 
No. of start pattern 
0 ~ 7 
1040H ~ 
1047H 
Number of steps in a pattern 
0 ~ 7 = N refers to the pattern will be executed from step 0 to step N. 
1050H ~ 
1057H 
Additional number of cycles for a pattern 
0 ~ 99 refers to the pattern will be executed for 1 ~ 100 times. 
1060H ~ 
1067H 
No. of the link pattern for the current 
pattern 
0 ~ 8. 8 refers to end of the program; 0 ~ 7 refers to the next pattern No. 
following the current pattern. 
2000H ~ 
203FH 
SV temperature for pattern0 ~ 7 
SV for pattern 0 is set in 2000H ~ 2007H 
-999 ~ 9,999 
2080H ~ 
20BFH 
Execution time for pattern 0 ~ 7 
Time for pattern 0 is set in 2080H ~ 
2087H 
0 ~ 900 (Every scale = 1 minute) 
3.  Address and content of the bit register (read bits are stored starting from LAB and written data is FF00H, set the 
bit as 1. 0000H sets the bit data as 0.) 
0810H 
Selecting communication write-in 
Communication write-in forbidden: 0 (default), allowed: 1 
0811H 
Selecting temperature unit 
0: °F; 1: °C/linear input (default) 
0812H 
Position of the decimal point 
0 or 1. Available for all modes except for thermocouple type B, S, R. 
0813H 
Read/write auto-tuning (AT) 
0: AT stops (default); 1: AT starts 
0814H 
RUN/STOP of the control 
0: stop; 1: run (default) 
0815H 
Programmable control RUN/STOP 
0: run (default); 1: stop 
0816H 
Programmable control RUN/PAUSE 
0: run (default); 1: pause 
0817H 
Read/write valve feedback 
0: without feedback (default); 1: with feedback 
0818H 
Read/write AT of valve feedback 
0: AT stops (default); 1: AT starts 
4.  Communication transmission format: command 01: read bit, 05: write bit, 03: read word, 06: write word. 
ASCII Mode 
Read Command 
Read Response Message 
Write Command 
Write Response Message 
Start word 
’:’ 
’:’ 
Start word 
’:’  ’:’ 
Start word 
’:’ 
’:’ 
Start word 
’:’ 
’:’ 
Machine address 1  ‘0’ 
‘0’ 
Machine address 1 
‘0’ 
‘0’  Machine address 1  ‘0’ 
‘0’ 
Machine address 1  ‘0’ 
‘0’ 
Machine address 0  ‘1’ 
‘1’ 
Machine address 0 
‘1’ 
‘1’  Machine address 0  ‘1’ 
‘1’ 
Machine address 0  ‘1’ 
‘1’ 
Command 1 
‘0’ 
‘0’ 
Command 1 
‘0’ 
‘0’ 
Command 1 
‘0’ 
‘0’ 
Command 1 
‘0’ 
‘0’ 
Command 0 
‘3’ 
‘1’ 
Command 0 
‘3’ 
‘1’ 
Command 0 
‘6’ 
‘5’ 
Command 0 
‘6’ 
‘5’ 
‘1’ 
‘0’ 
‘0’ 
‘0’ 
‘1’ 
‘0’ 
‘1’ 
‘0’ 
‘0’ 
‘8’ 
Length of response 
data (byte) 
‘4’ 
‘2’ 
‘0’ 
‘8’ 
‘0’ 
‘8’ 
‘0’ 
‘1’ 
‘0’ 
‘1’ 
‘0’ 
‘1’ 
‘0’ 
‘1’ 
Read start address 
of data/bit 
‘0’ 
‘0’ 
‘1’ 
‘7’ 
Write data address 
‘1’ 
‘0’ 
Write data address 
‘1’ 
‘0’ 
‘0’ 
‘0’ 
‘F’ 
‘0’ 
‘0’ 
‘F’ 
‘0’ 
‘F’ 
‘0’ 
‘0’ 
Data content in 
1000H/081xH 
‘4’ 
‘1’ 
‘3’ 
‘F’ 
‘3’ 
‘F’ 
‘0’ 
‘0’ 
‘0’ 
 ‘E’ 
‘0’ 
‘E’ 
‘0’ 
Read length of 
data/bit (word/bit) 
‘2’ 
‘9’ 
‘0’ 
 
Write data content 
‘8’ 
‘0’ 
Write data content 
‘8’ 
‘0’ 
LRC1 check 
‘E’ 
‘D’ 
‘0’ 
 LRC1 
 
‘F’ 
‘E’ 
LRC1  
‘F’ 
‘E’ 
LRC0 check 
‘A’ 
‘C’ 
Data content in 
1001H 
‘0’ 
 LRC 
 
‘D’ 
‘3’ 
LRC 0   
‘D’ 
‘3’ 
End word 1 
CR 
CR 
LRC1 check 
‘0’ 
‘E’ 
End word 1 
CR 
CR 
End word 1 
CR 
CR 
End word 0 
LF 
LF 
LRC0 check 
‘3’ 
‘3’ 
End word 0 
LF 
LF 
End word 0 
LF 
LF 
 
 
 
End word 1 
CR  CR 
 
 
 
 
 
 
 
 
 
End word 0 
LF 
LF 
 
 
 
 
 
 
LRC check: Sum up from “machine address” to “data content”, e.g. 01H + 03H + 10H + 00H + 00H + 02H = 16H. 
Obtain 2’s complement EA. 
 
RTU Mode 
Read Command 
Read Response Message 
Write Command 
Write Response Message 
Machine address  01H 
01H 
Machine address 
01H  01H  Machine address  01H 
01H  Machine address  01H 
01H 
Command 03H 
01H 
Command 03H  01H 
Command 06H 
05H 
Command 06H 
05H 
10H 
08H 
10H 
08H 
10H 
08H 
Read start 
address of data 
00H 
10H 
Length of response 
data (byte) 
04H  02H 
Write data 
address 
01H 
10H 
Write data 
address 
01H 
10H 
00H 
00H 
01H  17H 
03H 
FFH 
03H 
FFH 
Read length of 
data (bit/word) 
02H 
09H 
Data content 1 
F4H  01H 
Write data 
content 
20H 
00H 
Write data 
content 
20H 
00H 
CRC low byte 
C0H 
BBH 
03H 
 
CRC low byte 
DDH 
8FH 
CRC low byte 
DDH 
8FH 
CRC high byte 
CBH 
A9H 
Data content 2 
20H 
 
CRC high byte 
E2H 
9FH 
CRC high byte 
E2H 
9FH 
 
 
 
CRC low byte 
BBH  77H   
 
 
 
 
 
 
 
 
CRC high byte 
15H  88H   
 
 
 
 
 
CRC (Cyclical Redundancy Check) is obtained by the following steps. 
1. Load in a 16-bit register FFFFH as the CRC register. 
2. Do an exclusive OR operation of the first byte of the data and low byte of CRC register, and place the operation 
result back to the CRC register. 
3. Right shift the bits in the CRC register and fill the high bits with “0”. Check the removed lowest bit. 
4. If the removed lowest bit is “0”, repeat step 3. Otherwise, do an exclusive OR operation of the CRC register and the 
value A001H and place the operation result back to the CRC register. 
5. Repeat step 3 and 4 until the 8 bits (1 byte) are all right shifted.   
6. Repeat step 2 and 5 and calcualte all the bits to obtain CRC check. 
Please be aware of the high/low byte transmission order in the CRC register. 
 
 
How to Mount
 
 
 
How to Install Mounting Bracket
 
1. Insert DTV into the panel cutout 
2. Insert the mounting bracket into the mounting 
groove at the top and bottom of DTV. 
3. Push the mounting bracket forward until the 
bracket stops at the panel wall. 
4. Tighten the screw. 
     
 
         
 
 
 
Dimensions
 
DTV4896 DTV9696 
 
 
 
 
Panel Cutout
 
 
 
Terminals
 
DTV4896/DTV9696
 
DTV4896R/DTV9696R
 
60.0 min.
120
.0 min
.
110.0 min.
120
.0 min
.
48*96
96*96
44.5
+0.6
 0
91.
5
+0.6  0
91
+0.6  0
91
+0.6
 0
 
 
  
 
 
How to Set up Current Input
 
For normal input (default) 
Current input (4 ~ 20mA, 0 ~ 20mA) 
JU MPER
PIN HEADER
JP1
DEFAU LT SETTING
 
J UMPER
PIN HEADER
JP1
 
 
The content of this instruction sheet may be revised without prior notice. Please consult our distributors or   
download the most updated version at http://www.delta.com.tw/industrialautomation