4.  This function will consume 3 ~ 5 seconds more when you switch on DTE. 
 
 RS-485 Communication
 
1.  DTE supports baud rates 2,400/4,800/9,600/19,200/38,400/57,600/115,200 bps and does not support communication 
format 7, N, 1/8, E, 2/8, O, 2. Communication protocol = Modbus ASCII or RTU. 
2.  Function codes: H03 = read maximum 8 words in the register; H06 = write 1 word into the register. 
3.  Address and contents: Every parameter has 2 communication addresses. One is numbered by the function of the 
parameter, and the other is by the order of channel (as shown in the table below). 
 
 
INA 
INB 
Content 
Explanation 
CH1 
CH2 
CH3 
CH4 
CH5 
CH6 
CH7 
CH8 
Present 
temperature 
value/input error 
code 
Unit; 0.1 
See Table 5 
H1000 
(H1100) 
H1001 
(H1200) 
H1002 
(H1300) 
H1003 
(H1400) 
H1004 
(H1500) 
H1005 
(H1600) 
H1006 
(H1700) 
H1007 
(H1800) 
Set temperature 
value 
Unit: 0.1 
H1008 
(H1101) 
H1009 
(H1201) 
H100A 
(H1301) 
H100B 
(H1401) 
H100C 
(H1501) 
H100D 
(H1601) 
H100E 
(H1701) 
H100F 
(H1801) 
Max. temperature 
value 
Disabled when higher 
than default value 
H1010 
(H1102) 
H1011 
(H1202) 
H1012 
(H1302) 
H1013 
(H1402) 
H1014 
(H1502) 
H1015 
(H1602) 
H1016 
(H1702) 
H1017 
(H1802) 
Min. temperature 
value 
Disabled when lower 
than default value 
H1018 
(H1103) 
H1019 
(H1203) 
H101A 
(H1303) 
H101B 
(H1403) 
H101C 
(H1503) 
H101D 
(H1603) 
H101E 
(H1703) 
H101F 
(H1803) 
Error temperature 
value 
-999 ~ +999 
Unit: 0.1°C 
H1020 
(H1104) 
H1021 
(H1204) 
H1022 
(H1304) 
H1023 
(H1404) 
H1024 
(H1504) 
H1025 
(H1604) 
H1026 
(H1704) 
H1027 
(H1804) 
Proportional band 
value (Pb) 
0 ~ 9,999   
Unit: 0.1 
H1028 
(H1105) 
H1029 
(H1205) 
H102A 
(H1305) 
H102B 
(H1405) 
H102C 
(H1505) 
H102D 
(H1605) 
H102E 
(H1705) 
H102F 
(H1805) 
Ti value 
0 ~ 9,999 
H1030 
(H1106) 
H1031 
(H1206) 
H1032 
(H1306) 
H1033 
(H1406) 
H1034 
(H1506) 
H1035 
(H1606) 
H1036 
(H1706) 
H1037 
(H1806) 
Td value 
0 ~ 9,999 
H1038 
(H1107) 
H1039 
(H1207) 
H103A 
(H1307) 
H103B 
(H1407) 
H103C 
(H1507) 
H103D 
(H1607) 
H103E 
(H1707) 
H103F 
(H1807) 
Integration default 
0.0 ~ 100.0% 
Unit: 0.1% 
H1040 
(H1108) 
H1041 
(H1208) 
H1042 
(H1308) 
H1043 
(H1408) 
H1044 
(H1508) 
H1045 
(H1608) 
H1046 
(H1708) 
H1010 
(H1808) 
Proportional control 
offset error value, 
when Ti = 0 
0.0 ~ 100.0% 
Unit: 0.1% 
H1048 
(H1109) 
H1049 
(H1209) 
H104A 
(H1309) 
H104B 
(H1409) 
H104C 
(H1509) 
H104D 
(H1609) 
H104E 
(H1709) 
H104F 
(H1809) 
Proportional band 
coefficient of output 
1 and output 2 
0.01 ~ 99.99 
Unit: 0.01 
H1050 
(H110A) 
H1051 
(H120A) 
H1052 
(H130A) 
H1053 
(H140A) 
H1054 
(H150A) 
H1055 
(H160A) 
H1056 
(H170A) 
H1057 
(H180A) 
Dead band of 
control output 1 & 
output 2. 
-99.9 ~ 999.9 
H1058 
(H110B) 
H1059 
(H120B) 
H105A 
(H130B) 
H105B 
(H140B) 
H105C 
(H150B) 
H105D 
(H160B) 
H105E 
(H170B) 
H105F 
(H180B) 
Hysteresis for 
output 1 
0 ~ 9,999 
Unit: 0.1% 
H1060 
(H110C) 
H1061 
(H120C) 
H1062 
(H130C) 
H1063 
(H140C) 
H1064 
(H150C) 
H1065 
(H160C) 
H1066 
(H170C) 
H1067 
(H180C) 
Hysteresis for 
output 2 
0 ~ 9,999 
Unit: 0.1% 
H1068 
(H110D) 
H1069 
(H120D) 
H106A 
(H130D) 
H106B 
(H140D) 
H106C 
(H150D) 
H106D 
(H160D) 
H106E 
(H170D) 
H106F 
(H180D) 
Read/write output 
1 value 
Unit: 0.1 % 
H1070 
(H110E) 
H1071 
(H120E) 
H1072 
(H130E) 
H1073 
(H140E) 
H1074 
(H150E) 
H1075 
(H160E) 
H1076 
(H170E) 
H1077 
(H180E) 
Read/write output 
2 value 
Unit: 0.1 % 
H1078 
(H110F) 
H1079 
(H120F) 
H107A 
(H130F) 
H107B 
(H140F) 
H107C 
(H150F) 
H107D 
(H160F) 
H107E 
(H170F) 
H107F 
(H180F) 
Upper limit for 
alarm output 
Alarm enabled 
when temperature 
exceeds upper limit 
H1080 
(H1110) 
H1081 
(1210) 
H1082 
(H1310) 
H1083 
(H1410) 
H1084 
(H1510) 
H1085 
(H1610) 
H1086 
(H1710) 
H1087 
(H1810) 
Lower limit for 
alarm output 
Alarm enabled 
when temperature 
falls below lower 
limit 
H1088 
(H1111) 
H1089 
(H1211) 
H108A 
(H1311) 
H108B 
(H1411) 
H108C 
(H1511) 
H108D 
(H1611) 
H108E 
(H1711) 
H108F 
(H1811) 
Tuning for upper 
limit of analog 
output 
Current (4 ~ 20mA) 
or voltage output 
tuning 
H1090 
(H1112) 
H1091 
(H1212) 
H1092 
(H1312) 
H1093 
(H1412) 
H1094 
(H1512) 
H1095 
(H1612) 
H1096 
(H1712) 
H1097 
(H1812) 
Tuning for lower 
limit of analog 
output 
Current (4 ~ 20mA) 
or voltage output 
tuning 
H1098 
(H1113) 
H1099 
(H1213) 
H109A 
(H1313) 
H109B 
(H1413) 
H109C 
(H1513) 
H109D 
(H1613) 
H109E 
(H1713) 
H109F 
(H1813) 
Input sensor type 
See “Input” section 
H10A0 
(H1114) 
H10A1 
(H1214) 
H10A2 
(H1314) 
H10A3 
(H1414) 
H10A4 
(H1514) 
H10A5 
(H1614) 
H10A6 
(H1714) 
H10A7 
(H1814) 
Output function 
for output 1 
0: heating 
1: cooling 
2: proportional 
output 
H10A8 
(H1115) 
H10A9 
(H1215) 
H10AA 
(H1315) 
H10AB 
(H1415) 
H10AC 
(H1515) 
H10AD 
(H1615) 
H10AE 
(H1715) 
H10AF 
(H1815) 
Output function 
for output 2 
0: heating (default) 
1: cooling 
2: alarm 
H10B0 
(H1116) 
H10B1 
(H1216) 
H10B2 
(H1316) 
H10B3 
(H1416) 
H10B4 
(H1516) 
H10B5 
(H1616) 
H10B6 
(H1716) 
H10B7 
(H1816) 
Control method 
0: PID   
1: ON-OFF 
2: manual   
3: PID 
programmable 
H10B8 
(H1117) 
H10B9 
(H1217) 
H10BA 
(H1317) 
H10BB 
(H1417) 
H10BC 
(H1517) 
H10BD 
(H1617) 
H10BE 
(H1717) 
H10BF 
(H1817) 
Alarm 1 output 
mode 
See “Alarm Output” 
section 
H10C0 
(H1118) 
H10C1 
(H1218) 
H10C2 
(H1318) 
H10C3 
(H1418) 
H10C4 
(H1518) 
H10C5 
(H1618) 
H10C6 
(H1718) 
H10C7 
(H1818) 
Alarm 2 output 
mode 
See “Alarm Output” 
section 
H10C4 
(H1518) 
H10C5 
(H1618) 
H10C6 
(H1718) 
H10C7 
(H1818) 
 
 
 
 
Heating/cooling 
cycle for output 1 
1 ~ 99 seconds 
0 = 0.5 second 
H10C8 
(H1119) 
H10C9 
(H1219) 
H10CA 
(H1319) 
H10CB 
(H1419) 
H10CC 
(H1519) 
H10CD 
(H1619) 
H10CE 
(H1719) 
H10CF 
(H1819) 
Heating/cooling 
cycle for output 2 
1 ~ 99 seconds 
0 = 0.5 second 
H10D0 
(H111A) 
H10D1 
(H121A) 
H10D2 
(H131A) 
H10D3 
(H141A) 
H10D4 
(H151A) 
H10D5 
(H161A) 
H10D6 
(H171A) 
H10D7 
(H181A) 
 
 
INA 
INB 
Content 
Explanation 
CH1 
CH2 
CH3 
CH4 
CH5 
CH6 
CH7 
CH8 
Run/Stop the 
control 
0: stop 
1: executing 
2: program stops   
3: program pauses 
H10D8
(H111B)
H10D9
(H121B)
H10DA
(H131B)
H10DB
(H141B)
H10DC
(H151B)
H10DD 
(H161B) 
H10DE 
(H171B) 
H10DF 
(H181B) 
Status of PID 
auto-tuning 
0: stop 
1: executing 
H10E0
(H111C)
H10E1
(H121C)
H10E2
(H131C)
H10E3
(H141C)
H10E4
(H151C)
H10E5 
(H161C) 
H10E6 
(H171C) 
H10E7 
(H181C) 
Positive/negative 
proportional 
output 
0: positive 
1: negative (slope) 
H10E8
(H111D)
H10E9
(H121D)
H10EA
(H131D)
H10EB
(H141D)
H10EC
(H151D)
H10ED 
(H161D) 
H10EE 
(H171D) 
H10EF 
(H181D) 
Other statuses 
Other statuses 
H10F0
Temperature 
unit 
H10F1
Open special 
function
(H1234)
H10F2
Return to 
default
 
(H1357)
H10F3  
Reserved
H10F4  
Reserved
H10F5  
Reserved
 
H10F6  
Reserved
 
H10F7  
Reserved
 
Communication 
specifications 
See Table 4 
H10F8
Auto ID 
setup 
H10F9
Reserved
H10FA
Baud rate
H10FB
ASCII = 0 
RTU = 1 
H10FC
8 bits=0 
7 bits=1
H10FD 
2 stop=0 
1 stop=1
 
H10FE 
Parity 
H10FF 
Address 
1 ~ 247
 
Communication Parameter Setting: 
Content 
Baud rate 
2,400bps 
4,800bps 
9,600bps 
19,200bps
38,400bps
57,600bps 
115,200bps 
Parity bit 
None (N) 
Even (E) 
Odd (O) 
 
 
 
 
Table 4 
Error Codes: 
The error codes can be read from address H1000 ~ H1007. When the input operation is in normal status, H1000 ~ H1007 are 
for input values. When input error occurs (except for stable status and input exceeding the range), DTE will read error codes 
in H8001 ~ H8002. 
 
H1000 Error 
description 
H8001 
EEPROM cannot be written in. 
H8002 
Input sensor is not connected. 
H8003 
Group INB is not connected. 
Table 5 
Analog output current tuning scale: 1μA/scale 
Analog output voltage tuning scale: 1mV/scale 
Returning to Default Value: 
Write H1234 into address H10F1 and H1357 into address H10F2. Restart DTE. 
Programmable Communication Parameter Setting: 
 
 
INA 
INB 
Content 
Explanation
CH1
CH2
CH3
CH4
CH5
CH6 
CH7 
CH8 
Read remaining time of the step
Unit: sec 
H111E H121E H131E H141E H151E H161E  H171E  H181E 
Read remaining time of the step
Unit: min 
H111F
H121F H131F H141F H151F H161F  H171F  H181F 
Read the NO. of the current 
pattern 
0 ~ 7 
H1120
H1220
H1320
H1420
H1520
H1620  H1720  H1820 
Read the NO. of the current step
0 ~ 7 
H1121
H1221
H1321
H1421
H1521
H1621  H1721  H1821 
NO. of start pattern 
0 ~ 7 
H1122
H1222
H1322
H1422
H1522
H1622  H1722  H1822 
NO. of start step 
0 ~ 7 
H1123
H1223
H1323
H1423
H1523
H1623  H1723  H1823 
Programmable Parameter Setting: 
Content 
Explanation 
Pattern 
Pattern 
Pattern 
Pattern 
Pattern 
Pattern 
Pattern 
Pattern 
Max. number of 
steps in the pattern 
0 ~ 7 = N: The pattern 
executes from step 0 to 
N. 
H2068
H2069 H206A H206B H206C H206D H206E H206F 
Number of cycles of 
pattern 0 ~ 7 
execution 
0 ~ 199: The pattern 
has been executed for 1 
~ 200 times 
H2070
H2071
H2072
H2073
H2074
H2075 H2076 H2077 
NO. of current link 
pattern 
0 ~ 8: 8 refers to end of 
program; 0 ~ 7 refer to 
the NO. of next pattern 
H2078
H2079 H207A H207B H207C H207D H207E H207F 
 
Address 
Default 
Content 
Explanation 
2000H ~ 203FH 
Target temperatures for pattern 0 ~ 7 
Pattern 0: 2000H ~ 2007H 
Unit: 0.1°C 
2080H ~ 20BFH 
Execution time for pattern 0 ~ 7 
Pattern 0: 2080H ~ 2087H 
Time: 0 ~ 900 (Unit: 1 min) 
4.  Communication format: H03 = read bit data; H06 = write bit data 
ASCII Mode: 
Read Command 
Read Response Message 
Write Command 
Write Response Message 
Start word 
’:’
Start word 
’:’
Start word 
’:’
Start word 
’:’ 
Machine address 1 
‘0’
Machine address 1 
‘0’
Machine address 1 
‘0’
Machine address 1 
‘0’ 
Machine address 0 
‘1’
Machine address 0 
‘1’
Machine address 0 
‘1’
Machine address 0 
‘1’ 
Command 1 
‘0’
Command 1 
‘0’
Command 1 
‘0’
Command 1 
‘0’ 
Command 0 
‘3’
Command 0 
‘3’
Command 0 
‘6’
Command 0 
‘6’ 
Read Command 
Read Response Message 
Write Command 
Write Response Message
‘1’
‘0’
‘1’
‘1’
‘0’
Length of response data 
(byte) 
‘4’
‘0’
‘0’
‘0’
‘0’
‘0’
‘0’
Read start address of 
data/bit 
‘0’
‘1’
Data address 
‘1’
Data address 
‘1’
‘0’
‘F’
‘0’
‘0’
‘0’
Data content in H1000
‘4’
‘3’
‘3’
‘0’
‘0’
‘E’
‘E’
Read length of data/bit 
(word/bit) 
‘2’
‘0’
Write data content 
‘8’
Write data content 
‘8’
LRC1 check   
‘E’
‘0’
LRC1 check 
‘F’
LRC1 check 
‘F’
LRC0 check 
‘A’
Data content in H1001
‘0’
LRC0 check 
‘D’
LRC0 check 
‘D’
End word 1 
CR
LRC1 check   
‘0’
End word 1 
CR
End word 1 
CR
End word 0 
LF
LRC0 check 
‘3’
End word 0 
LF
End word 0 
LF
  
End 
word 
CR
    
  
End 
word 
LF
    
LRC Check: 
Sum up the contents from “machine address” to “data content”, e.g. H01 + H03 + H10 + H00 + H00 + H02 = H16. Obtain 
2’scomplement H EA.
 
RTU Mode: 
Read Command 
Read Response Message
Write Command 
Write Response Message 
Machine address 
H01
Machine address 
H01
Machine address 
H01
Machine address
H01
Command H03
Command H03
Command H06
Command H06
H10
H10
H10
Read start address of 
data 
H00
Length of response 
data (byte) 
H04
Write data address
H01
Write data address
H01
H00
H01
H03
H03
Read length of data 
(bit/word) 
H02
Data content 1 
HF4
Write data content
H20
Write data content
H20
CRC low byte 
HC0
H03
CRC low byte 
HDD
CRC low byte 
HDD
CRC high byte 
HCB
Data content 2 
H20
CRC high byte 
HE2
CRC high byte 
HE2
 
CRC low byte 
HBB
 
 
CRC high byte 
H15
 
CRC (Cyclical Redundancy Check) is obtained by the following steps: 
                            unsigned int reg_crc = 0xffff; 
i = 0; 
while (length--) 
{  reg_crc ^= RTUData[i]; 
      i ++; 
      for (j = 0; j < 8; j++) 
   {  if (reg_crc & 0x01)        reg_crc = (reg_crc >> 1) ^ 0xA001; 
            else                                          reg_crc = reg_crc >> 1; 
       
}   
}  
return(reg_crc); 
Software for Setting up Communication on PC: Download the free software on Delta’s website. 
 
 How to Mount & DIN Rail Size
 
 
 
 
Connect maximum 7 DTC2000 or DTC2001 controllers to DTE by using DIN rail. 
 
 
 
 
 
 
 
The content of this instruction sheet may be revised without prior notice. Please consult our distributor or 
download the most updated version at http://www.delta.com.tw/industrialautomation.