Power Factor
Phase power factor.
N/A
Environmental Sensors Information
Type (Name)
Type of the sensor.
Temperature-
Internal
Current information displays the actual alarm state of the current level based on the configured
thresholds when available. The alarm state can have one of the following values:
Tripped - when hardware overcurrent protection is tripped
High Critical - when the value is greater than the high critical threshold
High Warning - when the value is greater than the high warning threshold and less
than the high critical threshold
Low Warning - when the value is greater than the low critical threshold and less than
the low warning threshold
Low Critical - when the value is less than the low critical threshold
Voltage, Power Factor and Power Consumption display the Estimated or Measured value.
NOTE: Some power devices do not have the capability to read the real input voltage/power factor using proper
voltage/power factor sensors; in this case the values are configurable.
When recorded maximum value is provided by the PDU, it is shown in the same row of the
actual value.
To view and reset IPDU information:
1.
Select Applications - IPDU Power Mgmt. - View IPDUs Info. The View IPDUs Info screen
appears.
2.
To clear the stored maximum values, click the Clear or Reset button.
An administrator can select Expert Applications - IPDU Power Mgmt. - Configuration to
configure each configured IPDU.
NOTE: The operating parameters may differ depending on the make and model of IPDU.
Chapter 6: Applications