Brocade ICX 6650 Hardware Installation Guide
53-1002599-01
FRU removal and replacement procedures
5
4. Grasp the bail latch and pull the copper or fiber optic module out of the port.
FIGURE 17
Remove fiber optic module
5. Store the 
copper or 
fiber optic module in a safe, static-free place or in an anti-static bag.
6. Install a new 
copper or 
fiber optic module in the port.
Cabling a fiber optic module
For instructions on cabling a fiber optic module refer to 
Cleaning the fiber optic connectors
For instructions on cleaning a fiber optic module refer to 
FRU removal and replacement procedures
The field-replaceable units (FRUs) in the Brocade ICX 6650 can be removed and replaced without 
special tools. The switches can continue operating during the FRU replacement if the conditions 
specified in these procedures are followed. This covers both the power supply unit (PSU) FRUs and 
fan FRUs.
CAUTION
This document describes how to change FRUs for units with either an air intake or air exhaust. 
You must replace a failed FRU with a FRU of the same type. This applies to both power supplies 
and fans. A new FRU must have the same part number (P/N) as the FRU being replaced. The 
manufacturing P/N is located on the top of the FRU.
If a mismatched power source or fan assembly is installed by mistake, a warning is sent to the 
console. The warning messages will be similar to the following:
For a fan mismatch: [WARNING, Brocade ICX 6650, MISMATCH in Fan Air Flow direction. 
Replace FRU with fan air flows in the same direction.
For a power supply: [WARNING, Brocade ICX 6650, MISMATCH in PSU Air Flow direction. 
Replace PSU with air flows in the same direction