CONFIGURATION Menu
SR2MAN01 11/2007
61
FILTER Menu
Description
This function is used to detect more quickly any changes in states of Discrete inputs.
Two choices are available:
z
Fast,
z
Slow.
Response time:
This selection can only be made when the smart relay is in STOP. By default, the
smart relays are configured in SLOW.
smart relays are configured in SLOW.
Filter-Type
Selection
Selection
The current type is indicated by the selection symbol (black diamond).
Procedure for selection of filter type:
Filtering
Commutation
Response time
Slow
ON
→ OFF
5 milliseconds
OFF
→ ON
3 milliseconds
Fast
ON
→ OFF
0.5 milliseconds
OFF
→ ON
0.3 milliseconds
Note: This function is available on smart relays with a direct voltage power supply.
Note: to return to the main menu from the CONFIGURATION menu, use the
navigation key .
navigation key .
Step Action
1
Select the type of filtering using the
keys (the selection will flash).
2
Confirm with
Menu/OK.
Result: the display returns to the MAIN menu.