Schneider Electric TSXCUSBMBP Manual De Usuario

Descargar
Página de 63
Overview
12
35011984 02/2006
Modbus Plus Communication for Applications
Introduction
Most Win32 applications that support serial Modbus communications can 
communicate on a Modbus Plus network with the TSXCUSBMBP.
Virtual Serial 
Port (VSP)
A Virtual Serial Port (VSP) is used as the mechanism for redirecting communications 
from programs such as Concept, Unity, and ProWorx32 to the TSXCUSBMBP 
adapter. The VSP presents the same interface as a standard serial port to the 
software. As such it is indistinguishable from a physical serial port.
Modbus Plus 
Communication-
Process
The Modbus Plus Communication process is described in the following table:
Illustration: 
Routing Table
A routing table similar to that used by Modicon's BM85 Bridge Multiplexer is used to 
associate Modbus Slave IDs with 5-byte Modbus Plus routing paths. This allows the 
application software to communicate with any Modbus Plus device within range on 
a Modbus Plus network.
Stage Description
1
After the VSP is installed, it will create one serial port with the port reference (COM1-
COM12) defined in the TSXCUSBMBP Driver software.
2
When configuring the Modbus application software, this port reference for the VSP 
is selected as the serial port for the application to use.
3
The TSXCUSBMBP Driver will then work like a Bridge Multiplexer to redirect serial 
Modbus Plus messages onto a Modbus Plus network, but at a much faster rate since 
no serial communications are actually taking place.
Virtual
Serial Port
Driver
TSX C
 USB MBP
Driver
USB-MBP
Driver 
Application
Software
USB 
Controller
Windows XP
Operating System
USB-MBP
USB 
Cable
Modbus Plus Network