Schneider Electric TSXCUSBMBP Manual De Usuario

Descargar
Página de 63
35011984 02/2006
33
6
Connecting to a Modbus Plus 
Network
Modbus Plus Network Status Indicator
Introduction
The Modbus Plus Network Status Indicator displays the status of the Modbus Plus 
communications on the TSXCUSBMBP device. 
During initial monitoring of the network, the Indicator will flash at approximately 1 
time/second. If successful Modbus Plus communications are established, it will flash 
more rapidly, approximately 6 times/second. Otherwise, it will flash an error code, 
indicating that there is a problem with the connection.
Flash Codes
The table below indicates the valid flash codes for the Modbus Plus Network Status 
Indicator:
LED Flash Code Description
6 flashes/second
The TSXCUSBMBP is successfully receiving and passing the token on 
the Modbus Plus network. This is the normal operating mode for a node 
on a Modbus Plus network.
1 flash/second
The TSXCUSBMBP is offline, and monitoring the Modbus Plus network to 
determine which nodes are active prior to attempting to join the network.
2 flashes, then 
pause
The TSXCUSBMBP can hear the token being passed, but never 
receives the token.
3 flashes, then 
pause
The TSXCUSBMBP cannot hear the token being passed. This is the 
flash code to expect if the Modbus Plus cable is not connected to the 
TSXCUSBMBP.
4 flashes, then 
pause
The TSXCUSBMBP has detected another node on the Modbus Plus 
network using the same node address as the TSXCUSBMBP. The 
TSXCUSBMBP will remain in this state until it has not heard any messages 
from any other node with the same node address for at least 5 seconds.