Bard Dc3003 Manual De Usuario

Descargar
Página de 22
Manual 2100-484E
Page
20 of 22
7961-665C
Cooling
Heating
1st
Stage
2nd
Stage
3rd
Stage
4th
Stage
1st
Stage
4th
Stage
3rd
Stage
2nd
Stage
Lead
Unit
Unit
#1
Unit
#2
Dehumid.
Operation
Program
Advance
Comfort
Digital
Display
Temperature at Remote 1 sensor location*
Lead-lag-change-over time (1 to 30 days 
or 0 for disabled, Default is 7)
Cooling setpoint temperature 
(65 to 90 deg. F or 18 to 32 deg. C, Default is 75F/24C)
Temperature at local (main) Sensor 
Programming Display Menu
 Dehumidification Logic Enabled (Yes or No,
 Default is No)
Continuous blower operation
(None, Lead, Both, Default is lead)
High temperature alarm level 2 setpoint (70 to 120 deg. F
or 21 to 49 deg. C, Default is 90F/32C)
High temperature alarm level 1 setpoint (70 to 120 deg. F
or 21 to 49 deg. C, Default is 85F/24C)
Low temperature alarm setpoint (28 to 65 deg. F 
or -2 to 18 deg. C, Default is 50F/10C)
Increase compressor Turn On/Turn Off differential with
excessive compressor cycling (Yes or No, Default is Yes)
3 min. lead unit & 4 min. lag unit off-delay 
enabled (Yes or No, Default is No)
System 1 & 2 blowers run if delta T > 5F
between sensors (Yes or No, Default is Yes)
Power Loss Sys. 1
Power Loss Sys. 2
Refrig. Alarm Sys. 1
Refrig. Alarm Sys. 2
Fire/Smoke Alarm
Low Temp. Alarm
High Temp. Alarm 1
High Temp. Alarm 2
Lead/Lag Controller
Failure Alarm
Alarms
Save
Change
On
Off
To swap lead and lag unit positions press 
the ADVANCE button.
To enter the Program mode, press the 
PROGRAM button and release it when the 
message PROG, appears on the display. 
When in Program mode the DOWN and
UP arrows are used to scroll through the 
programming steps. 
A FLASHING display means that the 
function or choice is “SET”, and the 
display will alternate between the step 
function and setting.
To change the setting of any step press 
the CHANGE button and the display will 
stop flashing, allowing change to the 
setting by using the DOWN or UP arrows. 
When desired setting is reached press the 
SAVE button, and proceed as desired. 
When done with programming changes 
press the PROGRAM button until display 
stops flashing and room temperature 
display is shown. If no buttons are pushed
within 30-seconds the controller will 
automatically revert back to "RUN" mode.
Programming Instructions
Refer to Installation Instructions for complete details.
* If installed. If sensors are not installed, no display is shown.
  See label inside cover for sensor logic.
Locd
Controller is locked and no changes can be made.
Consult building authority.
Press COMFORT button once to reset 
to 72°F/22°C Cooling and 68°F/20°C 
Heating for 1-hour. Display will flash 
72 (or 22) during override period. Press 
2nd time to cancel during override if 
desired, or will automatically revert after
1-hour.
Comfort Mode
Note: On the DC3003 version the 
Lead/Lag Controller alarm light will 
"Flash" if Unit #3 has Power Loss 
or Refrig. Alarm. Open cover to 
observe Fault light that is on the 
alarm board located inside.
SP
Temperature at Outdoor sensor location*
DC Fan Operation (Edcf "emergency vent only",
Free "cooling", Both. Default is Both)
r I
Loc
Out
LLOC
cFAn
LoAL
HALI
HAL2
dFAn
Outdoor temperature setpoint for DC Fan 
operation.  Requires Outdoor Sensor (50-55-60F, Default is 55)
dFon
Deadband between cooling and heating setpoint
(2 to 20 deg. F or 1 to 11 deg. C, Default is 10F/5C)
db
dE9
Degrees shown in F or C (F or C, Default is F)
HuLE
CbdS
OFdE
Minimum 3 minute compressor run time
enabled (Yes or No, Default is No)
crun
CHYS
DC fan Purge duration in minutes
(No,1,2,3,4,5,6,7,8,9,10 Default is No)
Interval between DC Fan Purge cycles in Hours
(1,2,3,4,5,6,7,8,9,10 up to 24 Default is 1,
Pint display is suppressed if Purg is No)
Purg
Pint