Hoshizaki FD-1001MRH(-C) Manual De Usuario

Descargar
Página de 44
35
3. Infrared Sensor Shutdown Delay
This is the delay between the infrared sensor detecting ice and the start of the shutdown 
sequence. The infrared sensor shutdown delay is factory-adjusted to 100 seconds and 
no adjustment is required for most dispenser unit/storage bin applications. 
a) Standard Storage Bin: 
When installed on a standard storage bin, any shutdown delay setting is acceptable. 
b) Dispenser Unit:
For typical dispenser unit applications, a 100-second shutdown delay is recommended. 
However, on some dispenser unit applications, the ice level at shutoff may need to be 
adjusted depending on the dispenser agitation or dispense method. Should a different 
shutdown delay be desired, adjust S1 dip switch 1, , and 3 to obtain the shutdown 
delay needed. See the table below. For further details, contact Hoshizaki Technical 
Support at 1-800-33-1940.
Note: When the shutdown sequence begins, the compressor de-energizes immediately 
and then 5 minutes later the gear motor and fan motor de-energize.
 WARNING
Increasing the shutdown delay allows a higher level of ice in the dispensing 
unit/storage bin before shutdown. This could lead to icemaker movement or ice 
overflow. 
S1 Dip Switch
Shutdown Delay
NO. 1 NO. 2 NO. 3
OFF
OFF
OFF
0 seconds
ON
OFF
OFF
100 seconds (1.6 minutes)
OFF
ON
OFF
1100 seconds (18.3 minutes)
OFF
OFF
ON
1650 seconds (7.5 minutes)
ON
ON
OFF
00 seconds (36.7 minutes)
OFF
ON
ON
0 seconds
ON
ON
ON
0 Seconds