ALARM 1 ENABLE/DISABLE SUBMENU:
Press
b
5) Scroll though the available selection until
ENBL displays to
use Alarm 1.
Press
d
6) Display shows
STRD stored message momentarily and then
advances to
ABSo only, if it was changed, otherwise press a
to advance to
ABSo Alarm 1 Absolute/Deviation Submenu.
If
DSBL Alarm 1 Disabled was selected, all submenus of Alarm
1 Menu will be skipped and meter advances to
ALR2 Alarm 2
Menu. If
ENBL Alarm 1 Enabled was selected, Output 1 would
be automatically disabled, and reassigned as Alarm 1.
ALARM 1 ABSOLUTE/DEVIATION SUBMENU:
Press
d
7) Display flashes previous selection. Press
b to ABSo
Absolute or
_DEV Deviation.
Press
d
8) Display shows
STRD stored message momentarily and then
advances to
LTçH only, if it was changed, otherwise press a
to advance to
LTçH Alarm 1 Latch/Unlatch Submenu.
Absolute Mode allows Alarm 1 to function independently from Setpoint 1. If the
process being monitored does not change often, then "Absolute" Mode is
recommended.
process being monitored does not change often, then "Absolute" Mode is
recommended.
Deviation Mode allows changes to Setpoint 1 to be made automatically to
Alarm 1. Deviation Mode is typically the ideal mode if the process value changes
often. In Deviation Mode, set Alarm 1 a certain number of degrees or counts
away from Setpoint 1 — this relation remains fixed even if Setpoint 1 is changed.
Alarm 1. Deviation Mode is typically the ideal mode if the process value changes
often. In Deviation Mode, set Alarm 1 a certain number of degrees or counts
away from Setpoint 1 — this relation remains fixed even if Setpoint 1 is changed.
ALARM 1 LATCH/UNLATCH SUBMENU:
Press
d
9) Display flashes previous selection. Press
b to LTçH
Latched or
UNLT Unlatched.
Press
d
10) Display shows
STRD stored message momentarily and then
advances to
CT.CL only, if it was changed, otherwise press a to
advance to
CT.CL Contact Closure Submenu.
Latched Mode: Relay remains "latched" until reset. To reset already latched
alarm, select Alarm Latch and press
b twice (i.e. Unlatch and then back to
Latch) or from a Run Mode, push
d twice to put the controller in Standby Mode
and then push
d one more time to return to the Run Mode.
Unlatched Mode: Relay remains latched only as long as the alarm condition is
true.
true.