Carrier 50KQL-1PD Manual De Usuario

Descargar
Página de 36
26
Typical wiring schematics (cont)
MANUAL CHANGEOVER WITH DELUXE D CONTROLLER
FP2
CAP
PB
DELUXE D
CONTROL
BR 2
(HI)
UMT
PBS
OS
GROUND
LOG
TRANSFORMER
CR
BR 1
(LO)
S
JW1
LP
TEST
PINS
JW2
FP2
JW3
FP1 LOW
LOW
N.O.
ACC1
FUNCTIONS
ACC2
FUNCTIONS
H: HI FAN/DEHUMID
NOT USED
OFFON
S2
DIP SWITCH PACKAGE
S1
DIP SWITCH PACKAGE
OFFON
PM: DISABLE/ENABLE
UNIT STAGE: 2/1
T’STAT: HEAT COOL/HEAT PUMP
RV ON B/RV ON O
DEHUMID/NORMAL
NOT USED
BOILERLESS: ENABLE/DISABLE
BOILERLESS: 40
°F/50°F
SEE
NOTE 4
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
Y1
O/W2
G
R
C
AL1
W1
AL2
A
P3
R
C
ALARM
RELAY
SEE
NOTE 6
SEE
NOTE 7
NSB
ESD
OVR
H
P2
C
R
Y2
P1
R
R
COM
NC2
NO2
COM
NC1
NO1
RELAY
ACC1
RELAY
ACC2
1
2
3
4
5
6
7
8
COM2
COM1
R C S
C
JW4
AL2
DRY
RED
RED
2
3
2A
ORG
3A
RED GRY
YEL
ORG
YEL
UMT
2
3
PBS
1A
1B
YEL YEL YEL
ORG
DM
BRN
BRN
RED
TIME CLOCK
CLOSED-UNOCCUPIED
BRN
GRY
YEL
WHT
WV
WHT
RED
OS
NLL
GRY
GRY
PBS
RED
5
6
5A
6A
RED
7
7A
RED
GRY
P7
P6
CCG
24V
DC
EH1
EH2
BRN
CC
YEL
CR
1
COMPR
RELAY
0
FAN E N A B L E
RELAY
STATUS
TEST
FAULT
G
DELUXE D
MICROPROCESSOR
CONTROL LOGIC
1
2
RV RELAY
3
4
5
7
9
10
HP
L O C
FP1
RV
C O
HP
LOC
FP1
BRN
ORG
YEL
VIO
SEE
NOTE 4
FP2
CO
Y
R
GRY
C O M
NO
NC
COM
NO
FAN
S P E E D
R E L A Y
GRY
RED
RED
12
8
6
NOT USED
RVS
BLU
BRN
VIO
GRY
YEL
BLU
1
BLK
RED
BLK
ORG
230V
24V
TRANS
CB*
POWER SUPPLY
REFER TO DATA PLATE
USE COPPER CONDUCTORS ONLY.
SEE NOTE 2
REFER TO DISCONNECT
BOX FOR OPTIONAL
POWER SUPPLY CONNECTION
GROUND
L2
L1
OPTIONAL
CORD
CONNECTION
RED
NEUTRAL ON 265V
SYSTEMS
L2 (ribbed)
GROUND
L1 (plain)
PB
1
2
H
C
F
CAP
RED
RED
6
8
2
4
BLK
BLK
R
S
C
CR
BLU
COMPRESSOR
BRN
YEL
2
1
BM
B (HIGH)
A (LOW)
BLK
115
208
230
265
WHT
RED
ORG
BRN
LEAD COLOR
VOLTAGE
TRANSFORMER PRIMARY
LEAD COLORS
GRY
SEE
NOTE 3
PUSH BUTTON SWITCH ATTRIBUTES
X = CLOSED
O = OPEN
TERMINALS
1
2
3
4
5
6
7
8
1A 1B 2A 3A 4A 5A 6A 7A 8A
STOP
X O O O O O O O O
FAN ONLY X O O O O X O O O
LOW COOL O X X O O O X O O
HIGH COOL O X X O O O O X O
LOW HEAT X O O X X O X O O
HIGH HEAT X O O X X O O X X
BLOWER MOTOR WIRING
UNIT SIZE
POLE A
POLE B
07
5
3
09
5
4
12
4
3
15
4
3
19
4
3
AL
Alarm Relay Contacts
BM
Blower Motor
BR
Blower Relay
CAP
Capacitor
CB
Circuit Breaker
CO
Sensor, Condensate Overflow
CR
Compressor Relay
DM
Damper Motor
FP1
Sensor, Water Coil Freeze Protection
FP2
Sensor, Air Coil Freeze Protection
HP
High-Pressure Switch
JW1
Jumper Wire for Alarm
LOC
Loss of Charge Pressure Switch
NLL
Night Low Limit Switch
OS
Override Switch
PB
Power Terminal Block
PBS
Push Button Switch
PM
Performance Monitor
RVS
Reversing Valve Solenoid
TRANS
Transformer
UMT
Unit Mounted Thermostat
WV
Water Valve
----------
Field Line Voltage Wiring
Field Low-Voltage Wiring
LEGEND
Printed Circuit Trace
Relay/Contactor Coil
Solenoid Coil
Thermistor
Circuit Breaker
Relay Contacts-N.O.
Switch-Temperature
Switch-High Pressure
Switch-Low Pressure
Ground
Wire Nut
Mate-N-Lock
>>
*Optional wiring.
NOTES:
1.
Compressor and blower motor thermally protected
internally.
2.
All wiring to the unit must comply with local codes.
3.
Transformer is wired to 115-V (WHT) lead for 115/1/60
units, 265-V (BRN) lead for 265/1/60 units or 208-V
(RED) lead for 208/1/60 units.
For 203/1/60 switch RED and ORG leads at L1 and insu-
late RED lead.
Transformer is energy limiting or may have circuit
breaker.
4.
FP1 thermistor provides freeze protection for WATER.
When using ANTI-FREEZE solutions, cut JW3 jumper.
5.
Typical unit-mounted thermostat wiring shown.
6.
24-V alarm signal shown. For dry alarm contact, cut AL2
DRY (JW4) jumper and dry contact will be available
between AL1 and AL2.
7.
Transformer secondary ground via Deluxe D board
standoffs and screws to control box. (Ground available
from top two standoffs as shown.)