Lifebreath 94-EXCHANGER-MD Manual De Usuario

Descargar
Página de 24
5
At least 3' (1 m) away from the corner of the building*
At least 3’ away from gas meter, electric meter or a
walkway where fog or ice could create a hazard*
Not into a garage, workshop or other unheated space
When installing the weather hood, its outside perimeter
must be sealed with exterior caulking.
* Local code may require greater distances.
Intake Weather Hood Requirements
• Should be located upstream (if there are prevailing
winds) from the exhaust outlet
• At least 6' (2 m) from the exhaust weather hood *
• At least 6' (2 m) away from dryer vents and air handler
exhaust (medium or high efficiency furnaces)*
• A minimum of at least 6' (2 m) from driveways, oil fill
pipes, gas meters, or garbage containers, swimming
pools*
• At least 18" (457mm) above the ground, or above the
depth of expected snow accumulation*
• At least 3' (1 m) from the inside/outside corner of the
building*
• Do not locate in a garage, attic or crawl space
* Local code may require greater distances.
36" (1m)
recommended min.
36" (1m)
recommended min.
6' (2m)
recommended min.
18" (460mm) min.
18" (460mm) min.
OUTSIDE CORNER
INTAKE
EXHAUST
INSIDE CORNER
Weatherhood arrangement - requires a minimum of 6' 
(2m) separation and a minimum of 18" (460mm) 
clearance above the higher of the grade or anticipated 
snow level.
CAUTION
Weather Hood Clearances
Suspending the Unit using the
Provided Hanging Straps
Unit must be installed level to ensure proper 
condensate drainage.  Due to the broad range of 
installation and operational conditions, 
consideration must be given for the possibility 
of condensation forming on the unit or 
connecting ducting.  Objects below the 
installation may be exposed to condensate.
CAUTION
1. ThermalCollarslidesovergalvanized
sleeveofWeatherhood.
2. FastenThermalCollartoBelt.
3. SlidetheInsulatedFlexibleDuctingover
theWeatherhood'sgalvanizedsleeveand
fastenittotheThermalCollar.
4. Hoodishingedtoallowforeasyaccess
forcleaningofbirdscreen.
1/4"(6mm)SCREEN
(frontview)
EXTERIOR
WALL
SCREEN
(sideview)
COLLARISSUPPLIEDTO
ENSUREVAPOURBARRIER
IS100%SEALEDTO
WALLPLATE
12"galvanized
pipesupplied
Weatherhood Installation